11.6.11 Separate Setpoints

The Separate Setpoints strategy for AHU allows a Cut In/Cut Out setpoint to be set up for each heat and cool stage instead of just one cool and one heat setpoint set up for each stage (Normal strategy). Dehumidification con- trol can be performed while controlling with separate set- points.

11.6.12 AHU Zone Control

Unlike MultiFlex RTU rooftop controller applications, AHU applications are not required to be grouped into Zone applications (AHUs are usually large enough to be “zones” in and of themselves).

However, if desired, you may associate an AHU Con- trol application with a Zone application. The AHU will then use the Zone’s Temperature Control setpoints, occu- pancy state, summer/winter state, and economization and dehumidification enable signals. More information on Zone control is available in Section 11.7, Zone Control.

11.6.13 Hardware Overview

To set up an AHU for control by an E2, numerous tem- perature and humidity sensors for several different appli- cations must be connected to the I/O Network, as well as fan and cool proof checking devices, economization checking devices, curtailment devices, and all of the heat- ing, cooling, and dehumidification outputs.

Listed below are wiring instructions for some of the inputs and outputs that are part of a typical AHU setup.

Inputs

Sensor Type

Wiring

Instructions

 

 

 

 

 

Space Temperature

Temperature

See Table 9-1 on

 

 

page 9-3

 

 

 

Space Humidity

Humidity

See Table 9-1 on

 

 

page 9-3

 

 

 

Supply Air Temp

Temperature

See Table 9-1 on

 

 

page 9-3

 

 

 

Return Air Temp

Temperature

See Table 9-1 on

 

 

page 9-3

 

 

 

Outdoor Air Temp

Temperature

Set up as Out-

 

 

door Air Provider

 

 

in Global Data

 

 

(see Section

 

 

10.17).

 

 

 

Table 11-10- Suction Group Inputs

 

Inputs

Sensor Type

Wiring

Instructions

 

 

 

 

 

Outdoor Air Humid

Humidity

Set up as Out-

 

 

door Humidity

 

 

Provider in

 

 

Global Data (see

 

 

Section 10.17).

 

 

 

Curtailment Device

Digital

Set up as Curtail-

 

 

ment in Global

 

 

Data (see Sec-

 

 

tion 10.17).

 

 

 

Fan Proof

Digital

See Table 9-1 on

 

 

page 9-3

 

 

 

Fan Proof Reset

Digital

See Table 9-1 on

 

 

page 9-3

 

 

 

VS Inverter Alarm

Digital

See Table 9-1 on

 

 

page 9-3

 

 

 

Enthalpy Switch

Digital

See Table 9-1 on

(Indoor and/or Out-

 

page 9-3

door)

 

 

 

 

 

Dewpoint Probe (for

Dewpoint

See Table 9-1 on

Economization)

 

page 9-3

 

 

 

Mixed Air Temp (ana-

Temperature

See Table 9-1 on

log economizers only)

 

page 9-3

Table 11-10- Suction Group Inputs

11-24 E2 RX/BX/CX I&O Manual

026-1614 Rev 4 5-JAN-2013

Page 168