7 E2 Ethernet Peer Communications

Communication between E2 controller version 2.10 or greater may now be implemented through an Ethernet net- work using TCP/IP protocol. To utilize peer connections over Ethernet, the following tasks must be performed:

Upgrade the E2 controller firmware to version 2.10 or greater.

Install an industry-standard Ethernet switch(es) or hub(s) in an area or areas nearby the E2 controllers.

Install Ethernet straight-through cabling at the site from each E2 to the switch or hub. Installation of RJ-45 connectors may be necessary to achieve this goal. The recommended cabling is CAT 5.

7.1Ethernet IP

Configurations

If using an open network configuration (see Section 7.4.2, Open Network Layout), contact your IT Network Administrator for all IP configuration information (IP Address, Subnet Mask, Primary and Default Gateway set- tings).

7.2Hardware

Specifications

Standard industry-accepted practices for wiring of Ethernet networks are expected. E2 controllers use a star topology, identical to PC deployment. This includes a unique “point-to-point” run from a switch or hub to the controller (see Table 7-1for hub part numbers for order- ing). This is done with Category5 (or better) cable. Maxi- mum distance for a run of 10BaseT is 328 feet (100 meters) (11.5 dB loss max).

The maximum number of controllers allowed on an IP subnet is 20. All E2 controllers that must com- municate with each other must be on the same sub- net.

Recommended Ethernet cabling is CAT 5 (straight- through cable).

328 feet (100 meters) is the maximum distance allowed between devices before a switch or hub must be added.

7.2.1Components

Equipment Type

Specifications

 

 

Ethernet Five- or

* Industrial grade

Nine-port Switch

* Operating/storage temp range:

(may require an

-40°F to 185°F

additional power

* Vibration: IEC68-2-6

supply)

* RH: 5 to 95%

 

* UL 508A, CE approved

 

* Supports 10Base-T crossover

 

cable

 

* Supports all IEEE 802.3 proto-

 

col

 

* Supports Auto Crossover

 

MDI/MDI-X

 

* Screw-terminal power connec-

 

tors

 

 

Ethernet Surge

* Industrial grade

and Lightning

* Surge capacity: 1 kA / line

Protector (recom-

*Operating temp range: -40°F to

mended)

185°F

 

*Max frequency: 155 MHz

 

*Clamp and rated: 10V and 5V

 

 

10-Base-T/100-

Room Temperature (0 to 50 C)

Base-TX Hub

P/N 570-0100

 

 

10-Base-T/100-

Extended Temperature

Base-TX Hub

(-40 to 65 C) P/N 570-0200

 

 

Table 7-1- Equipment for E2 Ethernet Peer Communications

NOTE: An external power supply may be needed.

Ethernet IP Configurations

E2 Ethernet Peer Communications 7-1