Emerson E2 Setting the Fail-Safe Dip Switch, Relay Output Test Mode, Board Type Version

Models: E2

1 283
Download 283 pages 10.27 Kb
Page 105
Image 105

(all other output boards).

Table 9-3shows how the fail-safe switch, jumpers, and/or Form C contacts should be configured based on how you want the output to perform during both normal operation and during network/power loss.

Controller

 

 

Set Jumper

Fail

Set

or Wire

Command vs.

Switch

Form C

State

Contact State

To:

Contacts

 

 

 

 

To:

 

 

 

 

ON=CLOSED

ON

UP

N.C.

OFF=OPEN

 

 

 

 

 

 

 

ON=CLOSED

OFF

UP

N.O.

OFF=OPEN

 

 

 

 

 

 

 

ON=OPEN

ON

DOWN

N.O.

OFF=CLOSED

 

 

 

 

 

 

 

ON=OPEN

OFF

DOWN

N.C.

OFF=CLOSED

 

 

 

 

 

 

 

Table 9-3- Output Board Fail-Safe and Switch Settings

9.2.3Setting the Fail-Safe Dip

Switch

The fail-safe dip switch determines the sate of the relay when communication is lost between the board and E2. The fail-safe dip switches are labeled S2 on the 8RO, and switch S3 on the 8IO. Each of the eight rockers on the fail- safe dip switch corresponds to an output on the board. Set the rocker UP to close the relay and turn the output ON during network failure. Set the switch DOWN to open the relay and turn the output OFF during network failure.

9.2.4Relay Output Test Mode

Newly released versions of the MultiFlex I/O board family and the 8ROSMT have a new feature that allows relays to be manually energized and de-energized without use of an override from a Hand-Held Terminal when the board is offline. When a MultiFlex is in Relay Output Test Mode, the output fail-safe dip switches may be used to cycle the states of the relay outputs. The feature is designed to help manufacturers of panels test output wir- ing quickly and easily without need for a site controller or HHT.

Relay Output Test Mode is available in the following

product versions:

Board Type

Version

 

 

8RO-SMT output board

1.20F01

 

and above

 

 

MultiFlex 168, 88, 168AO,

1.60F01

and 88AO combination input/

and above

output boards

 

 

 

MultiFlex 168DO combina-

1.60F01

tion input/output boards with

and above

digital outputs

 

 

 

MultiFlex 1616LAO and

1.30F01

1616LDO combination input/

and above

output board

 

 

 

MultiFlex 1616L combina-

1.20F01

tion input/output board w/o

and above

analog outputs

 

 

 

To activate Relay Output Test Mode for MultiFlex, set switches 1-8 on DIP Switch banks S3 and S4 to the OFF (LEFT) position. For 8ROSMT, set switches 1-8 on DIP Switch bank S1 (NETWORK) to the OFF (DOWN) posi- tion. The board will enter Relay Output Test Mode.

In Relay Output Test Mode, fail-safe dip switches 1-8 (located on the output board layer of MultiFlex I/O boards, and next to switch bank S1 on the 8ROSMT) can be used to change the state of the relays.

Afail-safe switch in the ON position will cause the corresponding relay to be energized (i.e., OPEN on the N.C. terminals, and CLOSED on the N.O. terminals). A fail-safe switch in the OFF position will cause the relay to be de-energized (i.e., CLOSED on the N.C. terminals and OPEN on the N.O. terminals).

The LED that shows the output state will also be ON when the switch is ON and OFF when the switch is OFF.

To exit Relay Output Test Mode, set the address switches S3 and S4 to any position other than “all OFF.” The fail-safe switches will resume normal operation.

The 8RO, 8IO, and MultiFlex Outputs

Input and Output Setup 9-11

Page 105
Image 105
Emerson E2 Setting the Fail-Safe Dip Switch, Relay Output Test Mode, Output Board Fail-Safe and Switch Settings