Emerson operation manual E2 Installation Guide

Models: E2

1 283
Download 283 pages 10.27 Kb
Page 52
Image 52

E2 INSTALLATION GUIDE

1.Connect the I/O or MODBUS Network to one or all of the E2 RS485 I/O

or MODBUS Network ports. (A maximum of 31 devices can be wired to each I/O or MODBUS Network port.)

2. If the E2 is the beginning of all RS-485 I/O

 

 

 

 

 

or MODBUS Networks, set all three jumpers

 

 

 

5

 

to the UP position. For MODBUS, set the

 

 

3

4

jumpers in the top-most position (MOD). For

 

 

 

 

 

I/O Net, set the jumpers in the middle position

 

 

 

 

 

(I/O). For no termination, set the jumpers to

 

 

 

 

 

the DOWN position (NO).

 

 

 

 

 

 

3. Connect earth ground to one of the two

 

 

 

 

 

ground terminals provided. Use 12 AWG

 

 

 

 

 

(preferred) or 14 AWG wire and keep as

 

 

 

 

 

short as possible (less than 12 inches

 

 

 

 

 

preferred).

 

 

RS485 I/O or MODBUS Net

 

 

4. Connect 24VAC to the power terminals.

 

 

5. Flip the power switch to the ON position.

 

 

 

 

 

When 24VAC has been applied to the board,

MOD [

MOD[

MOD[

 

 

the green LED will illuminate.

 

 

 

 

I/O [

I/O [

I/O [

 

 

 

 

 

NO [

NO [

NO [

 

 

 

 

 

NOT TERMINATED

TERMINATED

TERMINATED

I/O or MODBUS Network

 

FOR I/O NET

FOR MODBUS NET

 

 

 

 

 

+

0V

_

Can be any COM port on the board

 

 

 

 

 

 

 

 

 

 

WHITE

SHIELD

BLACK

 

Earth

 

Ground

TO OTHER

Connector

RS485

 

DEVICES

 

12 or 14 AWG

OBSERVE WIRE

COLOR POLARITY

AC1

24VAC

AC1

24VAC

AC2

 

 

 

 

AC2

 

 

 

 

 

 

 

4-4 E2 RX/BX/CX I&O Manual

026-1614 Rev 4 5-JAN-2013

Page 52
Image 52
Emerson operation manual E2 Installation Guide