TIPS: ACKNOWLEDGEMENT VS. RESETTING

Reset an alarm if you believe the condition that caused it is fixed, but you wish for a new alarm to occur if the problem happens again.

You MUST reset an alarm that has been previ- ously acknowledged to re-enable alarming for the alarm. Failure to do so will cause the alarm to remain in ACK, and the alarm will not be gen- erated again. AN ACKNOWLEDGED ALARM WILL NOT AUTOMATICALLY RESET.

Acknowledge an alarm to silence alarm panel horns or lights, ONLY IF technicians have been notified of the problem and have been dis- patched. Technicians, after fixing the problem, MUST reset or clear the alarm to re-enable alarming.

To acknowledge an alarm or notice, highlight the desired log entry and press (ALARM ACK). A screen will come up prompting the user to either acknowl- edge the selected advisory, acknowledge all advisories, or to cancel the operation.

Press to acknowledge the selected advisory.

Press to acknowledge all advisories.

Press to cancel the operation.

12.10.8.2 Resetting

When a log entry is reset, it is forced to a normal con- dition and the log entry remains in the Controller Advisory Log.

An alarm, notice, or failure can be reset by highlight- ing a log entry and pressing (ALARM RST) while at the Advisory Log screen. A screen will come up prompt- ing the user to either reset the selected advisory, reset all advisories or to cancel the operation.

1.Press to reset the selected advisory.

2.Press to reset all advisories.

3.Press to cancel the operation.

12.10.8.3 Clearing

The option to clear logs completely removes a log entry from the Advisory Log.

Advisory Log entries may be cleared by highlighting the log entry and pressing (ALARM CLR) while viewing the Advisory Log screen. A screen will come up

prompting the user to either clear the selected advisory, clear all advisories or to cancel the operation.

1.Press to clear the selected advisory.

2.Press to clear all advisories.

3.Press to cancel the operation.Expanded Advi- sory Information

Figure 12-22- Expanded Info Screen

To view expanded information on a log entry, highlight the desired log and press (EXPD INFO). A screen will come up telling the user what advisory is being viewed out of a total number of advisories.

Property or Board/Point

This message shows the location where the advisory was generated. This will be a board and point address or an application input or output (in Area Ctrl:Applica- tion:Property) format.

Advisory Message

The advisory message is displayed below the Property or Board/Point. The Advisory Message describes the advi- sory log entry (what went wrong in the system).

Acknowledge Status

Acknowledge Status describes the state of the advi- sory. If an advisory has been acknowledged or reset, the user name or the person who acknowledged or reset the alarm will appear below the acknowledge status. The date and time when the advisory was acknowledged or reset will also be displayed below the user’s name.

If the advisory has not been acknowledged or reset, this field will display an asterisk “*” along with the word “UNK.”

Report Priority

The report priority fields describe the priority level of the advisory, as well as the date and time the advisory occurred.

Return To Normal

If the advisory has returned to a normal state, either on its own or because of a user-ordered alarm reset, the date