6

1.Connect the 4AO board to the RS485 I/O Network.

2.Set the network address on the first five

rockers of dip switch S1.

3.Set the network baud rate using rockers 6 and 7 of dip switch S1.

4.If the E2 is the beginning of all RS-485 I/O or MODBUS Networks, set all three jumpersto the UP position. For MODBUS, set thejumpers in the top-most position (MOD). ForI/O Net, set the jumpers in the middle position(I/O). For no termination, set the jumpers tothe DOWN position (NO).

5.Optionally, connect the 4-20mA outputs in either a 2-wire

or 4-wire hookup as illustrated in Step 5, or if a 4-20mA is not used, it may be left unconnected.

6.Connect board to the 24VAC center-tappedsecondary of the power transformer.

CAUTION: If you change any dip switch

VIN+

 

 

 

settings while the board is powered, disconnect

 

 

 

the power and re-power the board to reset.

 

 

 

15-K

NOTE: The voltage divide function capability

 

 

 

on the previous model (P/N 810-3030) 4AO board is

 

 

 

 

 

VOUT +

 

 

 

 

 

no longer supported. This can now be accomplished

 

 

 

15-K

by using two external 15-K resistors. If used with E2,

 

 

 

scale output range.

-

 

 

 

-

 

 

 

SHIELDED TWISTED PAIR

 

 

 

 

 

BAUD RATE

BELDEN #8761. FOR PLENUM,

 

 

 

 

 

 

USE BELDEN #82761 OR #88761

 

 

 

 

 

 

OR EQUIV.

 

 

 

 

 

 

 

 

 

 

 

 

 

NET

I/O

WIRE + to + (same color)

WIRE 0V to 0V

WIRE - to - (same color)

MOD [

MOD[

MOD[

 

 

 

 

 

 

 

I/O [

I/O [

 

I/O

[

 

 

 

 

 

 

 

NO [

NO [

 

NO

[

 

 

 

 

 

 

 

NOT TERMINATED

TERMINATED

 

 

TERMINATED

 

 

 

(Term)

 

 

FOR I/O NET

 

FOR MODBUS NET

(Term)

 

 

 

 

 

 

 

 

 

4-20mA

“2-wire” 4-20mA

 

 

 

 

 

4-20mA

 

 

“4-wire” 4-20mA

 

(Externally Powered)

 

 

 

Analog

 

 

(Internally Powered)

Analog

Hookup example.

 

 

 

 

Output

 

 

Hookup example.

Output

(Isolated)

 

 

 

+

 

+12V

Jumper

(Not Isolated)

 

+12V

Not Used

 

24V

 

 

 

 

 

 

_

 

+4-20

 

 

 

 

+4-20

+

 

 

 

 

 

 

+

 

 

4-20 OUT

_

 

 

 

 

 

4-20 OUT

 

250 ohms

-5V

 

 

 

 

 

 

0V

 

_

0V

Not Used

 

 

 

 

Note:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Either the “2-wire” or “4-wire”

 

 

 

 

250 ohms

 

1-5V

 

Hookup may be used at either

 

Grounded

 

 

 

 

 

 

4-20mA output. The Hookups may

 

 

 

 

 

 

 

 

 

be the same or different. If a 4-20mA

is not used, it may be left unconnected.

6 WIRING FOR 640-0056, 56VA Transformer, and 640-0080, 80VA Transformer

24VAC Center-Tapped Transformer

Power Wiring Types:

14 AWG

Belden 9495

18 AWG

Belden 9493

120/208/240 VAC

L2

(HOT)

(NEUTRAL)

 

L1

240

208

C

 

 

 

120

Three-conductor non-shielded cables are the recommended wire

for connecting between the center-tapped transformer and I/O boards.

AC1

0V

AC2

24V CT 24V

AC1

0V

AC2

PRIMARY SIDE

SECONDARY SIDE

 

6-18 E2 RX/BX/CX I&O Manual

026-1614 Rev 4 5-JAN-2013