Alarm Name

Default

Definition

Priority

 

 

 

 

 

Lost Log Data-CRC Error

30

An internal error has occurred in E2, resulting in lost

 

 

log data.

Low Battery Voltage

99

The backup battery that keeps the time and date resi-

 

 

dent on the E2 main board may need to be replaced.

Low Limit Alarm

User

An HVAC application (AHU, Zone, RT-100, or

 

 

ARTC/MultiFlex RTU) has a temperature below one

 

 

of its heating setpoints.

Low Limit Notice

50

Network variable low limit exceeded.

Low Pack Superheat

11

Multiflex Pak ProAct superheat low limit exceeded.

Low Suction Limit Exceeded

User

The suction pressure has fallen below a Suction

 

 

Group’s low suction setpoint.

MIP Receive Buffer Overflow

20

Messages from the Echelon network are coming into

 

 

E2 too fast for the controller to process. This might

 

 

be caused by an E2 having too many applications

 

 

and/or logs running, or there may be too many Eche-

 

 

lon devices on the same segment as the E2 (i.e., more

 

 

than 63). If this message persists, call Emerson Retail

 

 

Solutions service.

Modem Didn’t Initialize

20

E2 attempted to initialize the modem but failed.

Modem Init String Is Not Valid

30

The dial-out initialization string for the E2’s modem

 

 

is incorrect and may need editing.

Neuron Not Responding

20

The chip that handles Echelon networking on the E2

 

 

is either defective or in a mode that makes it non-

 

 

responsive. Contact Emerson Retail Solutions service

 

 

for assistance.

No Configuration Template

15

There is an internal error in the E2 software. Notify

 

 

Emerson Retail Solutions service.

No Description File

20

The Description File has failed to load onto the E2

 

 

when the Echelon device was commissioned. No

 

 

description file exists for the Open Echelon controller

 

 

being commissioned.

No Refrigerant flowing

Varies

Low or no refrigerant flowing.

 

depend-

 

 

ing on

 

 

applica-

 

 

tion type

 

No update has been received

Varies

No update has been received from the output point

 

depend-

connected to.

 

ing on

 

 

applica-

 

 

tion type

 

Normal Hi Limit Exceeded

User

An analog value has risen above its programmed Hi

 

 

Limit setpoint.

C-10 E2 RX/BX/CX I&O Manual