Alarm Name

Default

Definition

Priority

 

 

 

 

 

User Cleared All Applications

50

A user has cleared out all data from all applications in

 

 

this E2.

User/Appl. Forced Reset

50

A user or an application has forced a reset of this E2.

VS Alarm

20

Multiflex PAK variable speed device alarm.

VS Inverter Fail

User

A variable-speed inverter driving a variable-speed

 

 

fan or compressor has failed.

WCC Controller Alarm

20

Woodley case controller alarm.

WPK Controller Alarm

20

Woodley Pack Amps Fail alarm.

Watchdog Countdown Hit Zero

20

E2 locked up while trying to perform a task. If this

 

 

alarm occurs often, there may be a problem with your

 

 

system. Contact Emerson Retail Solutions service.

Watchdog Reset Timer Failed

20

E2 tried to reset itself to clear a hung task, but the

 

 

“watchdog” feature on the E2 was disabled. Check

 

 

the jumper J19 labeled “Watch Dog” on the E2 main

 

 

board. This jumper should be either be set to

 

 

“ENABLE” or it should not be present at all.

X300<->X300 Links Lost-CRC Err

20

An internal error has caused a loss of communication

 

 

between E2s.

C-14 E2 RX/BX/CX I&O Manual

026-1614 Rev 4 5-JAN-2013

Page 240
Image 240