SYMPTOM

POSSIBLE PROBLEM

SOLUTION

 

 

 

Problems with Temp Sensor or

16AI input dip switches are set

The 16 dip switches on the 16AI

Pressure Transducer Displaying

improperly.

board correspond to each of the

Proper Value

 

inputs:

 

 

Dip Switches Up = Temperature

 

 

Sensor

 

 

Dip Switches Down = Pressure

 

 

Transducer

 

 

 

 

Incorrect board and point

Set proper board and point set-

 

address.

tings for both input and output:

 

 

Go to the Inputs tab in the appli-

 

 

cation’s Setup screen and check

 

 

Board and Point.

 

 

 

 

Incorrect sensor type.

1. Verify that the sensor type in

 

 

E2 is the same as the sensor

 

 

installed. (For example, “5V-

 

 

200PSI” is a 5-volt powered

 

 

200PSI pressure transducer, and

 

 

“Temperature” is the standard

 

 

Emerson Retail Solutions tem-

 

 

perature sensor.

 

 

NOTE: The previous Eclipse

 

 

and Standard sensors are now

 

 

5V and 12V respectively.

 

 

2. From the Main Menu, select

 

 

System Configuration (7) and

 

 

Input Definitions (1).

 

 

3. Highlight the desired input

 

 

and press (SETUP) to

 

 

check Sensor Type.

 

 

 

No Heat or Air Will Come On

Incorrect board and points

Make sure that your board and

 

assignment.

points are assigned to the correct

 

 

compressors and heat stages

 

 

 

 

Check the Heat and Cool OAT

From the Home screen, press

 

lockout temps.

(AHU), (SETUP).

 

 

Move cursor to C5 (HT/CL

 

 

Setup) to check the Lockout

 

 

temperatures.

 

 

 