Maximum wet bulb temperature
27° C (80° F) Note: The upper limit of wet bulb temperature must be lowered 1.0° degree C for every 274 meters of elevation above 305 meters.
Relative humidity
8 - 80 percent
Typical heat load
550 watts or 1880 Btu/hr
Noise level
5.9 bels
The DS6000 should be maintained within an operating temperature range of 20 to 25 degrees Celsius (68 to 77 degrees Fahrenheit). The recommended operating temperature with the power on is 22 degrees Celsius (72 degrees Fahrenheit).
7.2.4 Preparing the rack
The DS6000 series requires an Electronic Industries Association (EIA)
Before you install the DS6000 series in a rack, keep in mind the following considerations:
Review the documentation that comes with your rack enclosure for safety and cabling considerations.
Install the DS6000 series in a recommended 22° C (72° F) environment.
To ensure rack stability, load the rack starting at the bottom.
If you install multiple components in the rack, do not overload the power outlets.
Always connect the storage server to a properly grounded outlet.
Always connect the rack power to at least two different power circuits or sources. This reduces the chance of a simultaneous loss of both AC power sources.
7.3System management interfaces
The DS6000 series provides the following management interfaces:
IBM TotalStorage DS Storage Manager
DS Open application programming interface
DS
You have to decide where you want to install this software.
7.3.1 IBM TotalStorage DS Storage Manager
The IBM TotalStorage DS Storage Manager is an interface that is used to perform logical configurations, service, copy services management, and firmware upgrades.
The DS Storage Manager software must be installed on a
Chapter 7. Installation planning | 119 |