Use the following steps to calculate the required space for your storage units:
1.Determine the dimensions of each model configuration in your storage units.
2.Determine the total space that is needed for the storage units by planning where you will place each storage unit in the rack.
3.Verify that the planned space and layout also meets the service clearance requirements for each unit.
7.2.2Power requirements
We describe here the input voltage requirements for the DS6000 series.
Input voltage requirements
The DS6000 series has
Table
Table 7-4 DS6000 series input voltage requirements
Characteristic | Value |
|
|
Nominal input voltages | |
| |
|
|
Minimum input voltage | 90 RMS V AC |
|
|
Maximum input voltage | 264 RMS V AC |
|
|
Input frequencies | 50 ± 3.0 Hz |
| 60 ± 3.0 Hz |
|
|
Two independent power outlets for the two DS6000 power line cords are needed by each base model and expansion model.
Important: To eliminate a single point of failure, the outlets must be independent. This means that each outlet must use a separate power source and each power source must have its own wall circuit breaker.
7.2.3 Environmental requirements
To properly maintain your DS6000 storage unit, you must install your storage unit in a location that meets the operating environment requirements.
Table
Table 7-5 Operating environment
Powered on temperature limit | 10 - 40° C (50 - 104° F) |
|
|
Powered off temperature limit | 10 - 52° C (50 - 126° F) |
|
|