2.9 Power subsystem

The power subsystem of the DS6800 consists of two redundant power supplies and two battery backup units (BBUs). DS6000 expansion enclosures contain power supplies but not BBUs. The power supplies convert input AC power to 3.3V, 5V, and 12V DC power. The battery units provide DC power, but only to the controller card memory cache in the event of a total loss of all AC power input. The DS6000 power supplies are hot swapable and a single power supply is able to support the power requirements of an entire enclosure. The second power supply is supplied by default, meaning you do not need to request redundant power as a feature.

Each power supply has two integrated fans for cooling the entire enclosure. If a power supply fails it should not be removed from the enclosure until a replacement one is available. Both power supplies must be physically present to ensure that cooling air flows correctly through the enclosure, even if one has failed. If during replacement of the failed supply, you take more than five minutes to install the new supply, the DS6000 may power off. Replacement, however, can be accomplished in less than 30 seconds.

AC power

Fault

detected

DC power

Figure 2-18 DS6000 power supplies

The DS6000 power supply has three indicators; they are defined in Table 2-3.Table 2-3 DS6000 power supply indicators

Indicator

Symbol

Purpose

 

 

 

AC Power (green)

AC

This indicator shows that main AC power is present. If it

 

 

is off then no AC power is being supplied to the power

 

 

supply, or the power supply is faulty.

 

 

 