10MAINTENANCE AND INSPECTION
10.2 Periodic Inspection
The items that must be inspected one or two times every 6 months to 1 year are listed below.
When the equipment is moved or modified, or layout of the wiring is changed, also perform this inspection.
Periodic Inspection
Item
1
2
3
4
5
| Inspection Item | Inspection | Judgment Criteria | Remedy | |
environment | Ambient |
| 0 to 55 °C |
| |
temperature |
|
| |||
|
|
| |||
|
|
| When the sequencer is | ||
|
| Measure with a thermometer |
| ||
| Ambient humidity | 5 to 95 %RH 1 | used in the board, the | ||
| and a hygrometer. | ambient temperature in | |||
Ambient |
| Measure corrosive gas. |
| the board becomes the | |
|
|
| ambient temperature. | ||
Atmosphere |
| Corrosive gas must not be | |||
|
| ||||
| present. |
| |||
|
| Measure a voltage across the | 85 to 132VAC | Change the power | |
|
| ||||
Power voltage | terminals of 100/200VAC and | 170 to 264VAC | |||
supply. | |||||
|
| 24VDC. |
| ||
|
| 15.6 to 31.2VDC | |||
|
| Further tighten screws. | |||
|
| Move the module to check for | The module must be installed | ||
| Looseness, rattling | If the CPU, I/O, or power | |||
Installation | looseness and rattling. | fixedly. | supply module is loose, | ||
Adhesion of dirt and | |||||
Check visually. | Dirt and foreign matter must | Remove and clean. | |||
|
|
|
| fix it with screws. | |
| foreign matter |
| not be present. |
| |
| Looseness of | Try to further tighten screws | Screws must not be loose. | Further tighten. | |
Connection | terminal screws | with a screwdriver. | |||
|
| ||||
Proximity of |
| Solderless terminals must be |
| ||
| solderless terminals | Check visually. | Correct. | ||
| positioned at proper intervals. | ||||
| to each other |
|
| ||
|
|
|
| ||
| Looseness of | Check visually. | Connectors must not be loose. | Further tighten connector | |
| connectors | fixing screws. | |||
|
|
|
| Even if the lowering of a | |
|
| check on the monitor mode of |
| battery capacity is not | |
|
|
| shown, replace the | ||
Battery | the GX Developer that SM51 or | (Preventive maintenance) | |||
battery with a new one if | |||||
|
| SM52 is turned OFF. |
| ||
|
|
| a specified service life of | ||
|
|
|
| ||
|
|
|
| the battery is exceeded. |
1 When AnS Series Module is included in the system, the judgement criteria will be from 10 to 90 % RH.
10 - 3 | 10 - 3 |