11 TROUBLESHOOTING

MELSEC-Q

Special Relay List

(1) Diagnostic Information

Number

Name

 

Meaning

 

Explanation

Set by

Corresponding

Applicable

 

 

(When Set)

ACPU

CPU

 

 

 

 

 

 

M9

 

 

 

 

 

 

 

 

 

 

 

 

• ON if diagnosis results show error occurrence

 

 

 

 

 

OFF: No error

(Includes when an annunciator is ON, and when an error

 

 

 

SM0

Diagnostic errors

is detected with CHK instruction)

S (Error)

New

 

ON

: Error

 

 

 

 

 

• Stays ON subsequently even if normal operations

 

 

 

 

 

 

 

restored

 

 

 

 

 

 

 

 

• Comes ON when an error occurs as a result of self-

 

 

 

 

Self-diagnosis

OFF: No self-diagnosis

diagnosis. (Does not include when annunciator is ON or

 

 

 

SM1

 

errors

when error is detected by CHK instruction.)

S (Error)

M9008

 

error

 

 

 

ON

: Self-diagnosis

• Stays ON subsequently even if normal operations

 

 

 

 

 

 

 

 

 

 

 

 

restored

 

 

 

+Rem

 

 

OFF: No error common

 

 

 

 

 

SM5

Error common

 

information

• When SM0 is ON, ON if there is error common

S (Error)

New

 

information

ON

: Error common

information

 

 

 

 

 

 

 

 

 

 

information

 

 

 

 

 

 

 

OFF: No error common

 

 

 

 

 

SM16

Error individual

 

information

• When SM0 is ON, ON if there is error individual

S (Error)

New

 

information

ON

: Error common

information

 

 

 

 

 

 

 

 

 

 

information

 

 

 

 

 

SM50

Error reset

OFF

ON : Error reset

• Conducts error reset operation

U

New

 

 

 

 

 

• ON if battery voltage at CPU module or memory card

 

 

 

SM51

Battery low latch

OFF: Normal

drops below rated value. Stays ON subsequently even

S (Error)

M9007

 

ON

: Battery low

after normal operation is restored

 

 

 

 

 

 

 

 

 

 

• Synchronous with BAT. ALA/BAT. LED

 

 

 

SM52

Battery low

OFF: Normal

• Same as SM51, but goes OFF subsequently when

S (Error)

M9006

 

ON

: Battery low

battery voltage returns to normal.

 

 

 

 

 

 

 

 

 

 

• Comes ON it a momentary power interruption of less

 

 

 

 

 

 

 

than 20ms occurred during use of the AC power supply

 

 

 

 

 

OFF: AC/DC DOWN not

module, and reset by turning the power OFF, then ON.

 

 

 

 

 

• Comes ON if a momentary power interruption of less

 

 

 

 

AC/DC DOWN

 

detected

 

 

 

SM53

 

than 10ms occurred during use of the DC power supply

S (Error)

M9005

QCPU

detection

ON : AC/DC DOWN

 

module, and reset by turning power OFF, then ON.

 

 

 

 

 

 

detected

 

 

 

 

 

 

• Comes ON if a momentary power interruption of less

 

 

 

 

 

 

 

 

 

 

 

 

 

 

than 1ms occurred during use of the DC power supply

 

 

QnA

 

 

 

 

module, and reset by turning power OFF, then ON.

 

 

 

 

 

 

 

• Goes ON if MINI (S3) link error is detected at even one of

 

 

 

SM54

MINI link errors

OFF: Normal

the installed MELSECNET/MINI master modules.

S (Error)

M9004

QnA

ON

: Error

Stays ON subsequently even after normal operation is

 

 

 

 

 

 

 

 

 

restored.

 

 

 

 

 

 

OFF: Normal

• ON when operation error is generated

 

 

 

SM56

Operation Errors

• Stays ON subsequently even if normal operations

S (Error)

M9011

 

ON

: Operation error

 

 

 

 

 

restored

 

 

 

 

 

 

 

 

• Comes ON even if there is only one output module with a

 

 

 

SM60

Blown fuse

OFF: Normal

blown fuse, and remains ON even after return to normal

S (Error)

M9000

 

detection

ON

: Module with blown fuse

• Blown fuse status is checked even for remote I/O station

 

 

 

 

 

 

 

 

 

output modules.

 

 

 

+Rem

 

 

 

 

• Comes ON if there is a discrepancy between the actual

 

 

 

I/O module

OFF: Normal

I/O modules and the registered information when the

 

 

 

SM61

power is turned on

 

S (Error)

M9002

 

verification error

ON

: Error

 

 

 

• I/O module verification is also conducted for remote I/O

 

 

 

 

 

 

 

 

 

 

 

 

 

 

station modules.

 

 

 

 

 

Annunciator

OFF: Not detected

 

 

S

 

 

SM62

• Goes ON if even one annunciator F goes ON.

(Instruction

M9009

 

detection

ON

: Detected

 

 

 

 

execution)

 

 

 

 

 

 

 

 

 

 

 

 

OFF: Not detected

• Goes ON if error is detected by CHK instruction.

S

 

 

SM80

CHK detection

• Stays ON subsequently even after normal operation is

(Instruction

New

 

ON : Detected

 

 

 

restored.

 

execution)

 

 

 

 

 

 

 

 

 

SM90

 

 

 

Corresponds to SD90

 

 

M9108

 

SM91

 

 

 

Corresponds to SD91

 

 

M9109

 

SM92

Startup of

OFF: Not started

Corresponds to SD92

• Goes ON when measurement of

 

M9110

 

SM93

watchdog timer

Corresponds to SD93

 

M9111

 

 

(watchdog timer reset)

step transition watchdog timer is

 

 

SM94

for step transition

 

Corresponds to SD94

 

M9112

 

ON : Started

commenced.

U

 

SM95

(Enabled only

Corresponds to SD95

M9113

 

 

(watchdog timer

• Resets watchdog timer when it

 

 

SM96

when SFC

 

Corresponds to SD96

 

M9114

 

 

started)

goes OFF.

 

 

 

program exists)

 

 

 

 

 

SM97

 

Corresponds to SD97

 

New

 

 

 

 

 

 

SM98

 

 

 

Corresponds to SD98

 

 

New

 

SM99

 

 

 

Corresponds to SD99

 

 

New

 

11 - 43

 

 

 

 

 

11 - 43