11 TROUBLESHOOTING
11.2.16 Flowchart for when UNIT VERIFY ERR. occurs
The following shows the flowchart to be followed when UNIT VERIFY ERR. occurs at PLC
UNIT. VERIFY ERR. occurs.
Check the slot where error occurred with the GX Developer.
Is the module of | NO |
|
|
|
|
|
|
| ||
|
|
| Install the module properly. |
| ||||||
the applicable slot installed |
|
|
|
|
| |||||
|
|
|
|
| ||||||
properly? |
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
| |||
| YES |
| NO |
|
| YES | ||||
|
|
|
| |||||||
|
|
|
| |||||||
|
|
|
| Is the "ERR." LED | ||||||
|
|
|
|
|
|
|
| turned off? |
| |
|
|
|
|
|
|
|
|
|
| |
Are all the | NO |
|
|
|
|
|
|
| ||
extension cables of the |
|
|
|
|
|
|
| |||
|
|
| Install the extension cable properly. |
| ||||||
base module connected |
|
|
|
|
|
| ||||
properly? |
|
|
|
|
|
|
|
| ||
| YES |
| NO |
|
| YES | ||||
|
|
|
| |||||||
|
| Is the "ERR." LED | ||||||||
|
|
|
| |||||||
|
|
|
|
|
|
|
| turned off? |
| |
|
|
| Proper operation |
|
|
| ||||
Replace the applicable module. |
|
|
| |||||||
|
|
|
|
|
|
|
| |||
| Error detection |
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
| ||
|
|
| Proper operation |
|
|
| ||||
Replace the CPU module. |
|
|
| |||||||
|
|
|
|
|
|
|
| |||
| Error detection |
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
| ||
|
| Proper operation |
|
|
| |||||
Replace the applicable |
|
|
| |||||||
base unit. |
|
|
|
|
|
|
|
|
Error detection
Hardware fault
Please consult your local Mitsubishi service center or representative, explaining a detailed description
of the problem. Completion
11 - 16 | 11 - 16 |