11 TROUBLESHOOTING

MELSEC-Q

Special Relay List

(2) System information

Number

Name

 

Meaning

Explanation

Set by

Corresponding

Applicable

 

(When Set)

ACPU

CPU

 

 

 

 

 

M9

 

 

 

 

 

 

 

SM202

LED OFF

OFF

ON : LED OFF

• When this relay goes from OFF to ON, the LEDs

U

New

 

 

command

 

 

corresponding to the individual bits at SD202 go off

 

 

 

SM203

STOP contact

STOP status

• Goes ON at STOP status

S (Status

M9042

 

change)

 

 

 

 

 

 

 

 

SM204

PAUSE contact

PAUSE status

• Goes ON at PAUSE status

S (Status

M9041

 

change)

 

 

 

 

 

 

 

 

SM205

STEP-RUN

STEP-RUN status

• Goes ON at STEP-RUN status

S (Status

M9054

 

 

contact

 

 

 

change)

 

 

 

PAUSE enable

OFF: PAUSE disabled

• PAUSE status is entered if this relay is ON when the

U

M9040

 

 

coil

ON

: PAUSE enabled

remote PAUSE contact goes ON

 

 

 

 

 

SM206

Device test

OFF: Device test not yet

• Comes ON when the device test mode is executed on

 

 

 

 

request

 

executed

S (Request)

New

Remote

 

acceptance

 

GX Developer.

 

ON

: Device test executed

 

 

 

 

status

 

 

 

 

 

 

 

 

 

 

 

 

Clock data set

OFF: Ignored

• When this relay goes from OFF to ON, clock data being

 

 

 

SM210

stored from SD210 to SD213 after execution of END

U

M9025

 

request

ON

: Set request

 

 

 

 

 

instruction for changed scan is written to the clock device.

 

 

 

SM211

Clock data error

OFF: No error

• ON when error is generated in clock data (SD210 to

S (Request)

M9026

 

ON

: Error

SD213) value, and OFF if no error is detected.

 

 

 

 

 

 

 

Clock data

OFF: Ignored

• Displays clock data as month, day, hour, minute, and

 

 

Q3A

SM212

U

M9027

Q4A

display

ON : Display

second at the LED display at front of CPU module.

 

 

 

 

 

 

 

Q4AR

SM213

Clock data read

OFF: Ignored

• When this relay is ON, clock data is read to SD210 to

U

M9028

+Rem

request

ON : Read request

SD213 as BCD values.

 

 

 

 

• Goes OFF when reset of the PLC No. 1 is canceled.

 

 

 

SM240

No. 1 CPU reset

OFF: PLC No. 1 reset cancel

• Comes ON when the PLC No. 1 is resetting (including

 

 

 

 

flag

ON

: PLC No. 1 resetting

the case where the PLC is removed from the base unit).

 

 

 

 

 

 

 

The other PLCs are also put in reset status.

 

 

 

 

 

 

 

• Goes OFF when reset of the PLC No. 2 is canceled.

 

 

 

 

No. 2 CPU reset

OFF: PLC No. 2 reset cancel

• Comes ON when the PLC No. 2 is resetting (including

 

 

 

SM241

flag

ON

: PLC No. 2 resetting

the case where the PLC is removed from the base unit).

 

 

 

 

 

 

 

The other PLCs result in "MULTI CPU DOWN" (error

 

 

 

 

 

 

 

code: 7000).

 

 

 

 

 

 

 

• Goes OFF when reset of the PLC No. 3 is canceled.

 

 

 

 

No. 3 CPU reset

OFF: PLC No. 3 reset cancel

• Comes ON when the PLC No. 3 is resetting (including

 

 

 

SM242

flag

ON

: PLC No. 3 resetting

the case where the PLC is removed from the base unit).

 

 

 

 

 

 

 

The other PLCs result in "MULTI CPU DOWN" (error

 

 

 

 

 

 

 

code: 7000).

 

 

 

 

 

 

 

• Goes OFF when reset of the PLC No. 4 is canceled.

S (Status

 

QCPU

 

No. 4 CPU reset

OFF: PLC No. 4 reset cancel

• Comes ON when the PLC No. 4 is resetting (including

New

function

 

change)

SM243

flag

ON

: PLC No. 4 resetting

the case where the PLC is removed from the base unit).

 

 

Ver. B

 

 

 

 

The other PLCs result in "MULTI CPU DOWN" (error

 

 

 

 

 

 

 

code: 7000).

 

 

 

 

No. 1 CPU error

OFF: PLC No. 1 normal

• Goes OFF when the PLC No. 1 is normal (including a

 

 

 

SM244

ON

: PLC No. 1 during stop

continuation error).

 

 

 

flag

 

 

 

 

 

 

error

• Comes ON when the PLC No. 1 is during a stop error.

 

 

 

 

No. 2 CPU error

OFF: PLC No. 2 normal

• Goes OFF when the PLC No. 2 is normal (including a

 

 

 

SM245

ON

: PLC No. 2 during stop

continuation error).

 

 

 

flag

 

 

 

 

 

 

error

• Comes ON when the PLC No. 2 is during a stop error.

 

 

 

 

No. 3 CPU error

OFF: PLC No. 3 normal

• Goes OFF when the PLC No. 3 is normal (including a

 

 

 

SM246

ON

: PLC No. 3 during stop

continuation error).

 

 

 

flag

 

 

 

 

 

 

error

• Comes ON when the PLC No. 3 is during a stop error.

 

 

 

 

No. 4 CPU error

OFF: PLC No. 4 normal

• Goes OFF when the PLC No. 4 is normal (including a

 

 

 

SM247

ON

: PLC No. 4 during stop

continuation error).

 

 

 

flag

 

 

 

 

 

 

error

• Comes ON when the PLC No. 4 is during a stop error.

 

 

 

11 - 44

11 - 44