11 TROUBLESHOOTING
Special Relay List
(2) System information
Number | Name |
| Meaning | Explanation | Set by | Corresponding | Applicable | |
| (When Set) | ACPU | CPU | |||||
|
|
|
|
| M9 | |||
|
|
|
|
|
|
| ||
SM202 | LED OFF | OFF | ON : LED OFF | • When this relay goes from OFF to ON, the LEDs | U | New |
| |
| command |
|
| corresponding to the individual bits at SD202 go off |
|
|
| |
SM203 | STOP contact | STOP status | • Goes ON at STOP status | S (Status | M9042 |
| ||
change) |
| |||||||
|
|
|
|
|
|
| ||
SM204 | PAUSE contact | PAUSE status | • Goes ON at PAUSE status | S (Status | M9041 |
| ||
change) |
| |||||||
|
|
|
|
|
|
| ||
SM205 | • Goes ON at | S (Status | M9054 |
| ||||
| contact |
|
|
| change) |
|
| |
| PAUSE enable | OFF: PAUSE disabled | • PAUSE status is entered if this relay is ON when the | U | M9040 |
| ||
| coil | ON | : PAUSE enabled | remote PAUSE contact goes ON |
| |||
|
|
|
| |||||
SM206 | Device test | OFF: Device test not yet | • Comes ON when the device test mode is executed on |
|
|
| ||
| request |
| executed | S (Request) | New | Remote | ||
| acceptance |
| GX Developer. | |||||
| ON | : Device test executed |
|
|
| |||
| status |
|
|
|
| |||
|
|
|
|
|
|
| ||
| Clock data set | OFF: Ignored | • When this relay goes from OFF to ON, clock data being |
|
|
| ||
SM210 | stored from SD210 to SD213 after execution of END | U | M9025 |
| ||||
request | ON | : Set request |
| |||||
|
|
|
| instruction for changed scan is written to the clock device. |
|
|
| |
SM211 | Clock data error | OFF: No error | • ON when error is generated in clock data (SD210 to | S (Request) | M9026 |
| ||
ON | : Error | SD213) value, and OFF if no error is detected. |
| |||||
|
|
|
|
| ||||
| Clock data | OFF: Ignored | • Displays clock data as month, day, hour, minute, and |
|
| Q3A | ||
SM212 | U | M9027 | Q4A | |||||
display | ON : Display | second at the LED display at front of CPU module. | ||||||
|
|
|
|
|
|
| Q4AR | |
SM213 | Clock data read | OFF: Ignored | • When this relay is ON, clock data is read to SD210 to | U | M9028 | +Rem | ||
request | ON : Read request | SD213 as BCD values. | ||||||
|
|
|
| • Goes OFF when reset of the PLC No. 1 is canceled. |
|
|
| |
SM240 | No. 1 CPU reset | OFF: PLC No. 1 reset cancel | • Comes ON when the PLC No. 1 is resetting (including |
|
|
| ||
| flag | ON | : PLC No. 1 resetting | the case where the PLC is removed from the base unit). |
|
|
| |
|
|
|
| The other PLCs are also put in reset status. |
|
|
| |
|
|
|
| • Goes OFF when reset of the PLC No. 2 is canceled. |
|
|
| |
| No. 2 CPU reset | OFF: PLC No. 2 reset cancel | • Comes ON when the PLC No. 2 is resetting (including |
|
|
| ||
SM241 | flag | ON | : PLC No. 2 resetting | the case where the PLC is removed from the base unit). |
|
|
| |
|
|
|
| The other PLCs result in "MULTI CPU DOWN" (error |
|
|
| |
|
|
|
| code: 7000). |
|
|
| |
|
|
|
| • Goes OFF when reset of the PLC No. 3 is canceled. |
|
|
| |
| No. 3 CPU reset | OFF: PLC No. 3 reset cancel | • Comes ON when the PLC No. 3 is resetting (including |
|
|
| ||
SM242 | flag | ON | : PLC No. 3 resetting | the case where the PLC is removed from the base unit). |
|
|
| |
|
|
|
| The other PLCs result in "MULTI CPU DOWN" (error |
|
|
| |
|
|
|
| code: 7000). |
|
|
| |
|
|
|
| • Goes OFF when reset of the PLC No. 4 is canceled. | S (Status |
| QCPU | |
| No. 4 CPU reset | OFF: PLC No. 4 reset cancel | • Comes ON when the PLC No. 4 is resetting (including | New | function | |||
| change) | |||||||
SM243 | flag | ON | : PLC No. 4 resetting | the case where the PLC is removed from the base unit). |
|
| Ver. B | |
|
|
|
| The other PLCs result in "MULTI CPU DOWN" (error |
|
|
| |
|
|
|
| code: 7000). |
|
|
| |
| No. 1 CPU error | OFF: PLC No. 1 normal | • Goes OFF when the PLC No. 1 is normal (including a |
|
|
| ||
SM244 | ON | : PLC No. 1 during stop | continuation error). |
|
|
| ||
flag |
|
|
| |||||
|
|
| error | • Comes ON when the PLC No. 1 is during a stop error. |
|
|
| |
| No. 2 CPU error | OFF: PLC No. 2 normal | • Goes OFF when the PLC No. 2 is normal (including a |
|
|
| ||
SM245 | ON | : PLC No. 2 during stop | continuation error). |
|
|
| ||
flag |
|
|
| |||||
|
|
| error | • Comes ON when the PLC No. 2 is during a stop error. |
|
|
| |
| No. 3 CPU error | OFF: PLC No. 3 normal | • Goes OFF when the PLC No. 3 is normal (including a |
|
|
| ||
SM246 | ON | : PLC No. 3 during stop | continuation error). |
|
|
| ||
flag |
|
|
| |||||
|
|
| error | • Comes ON when the PLC No. 3 is during a stop error. |
|
|
| |
| No. 4 CPU error | OFF: PLC No. 4 normal | • Goes OFF when the PLC No. 4 is normal (including a |
|
|
| ||
SM247 | ON | : PLC No. 4 during stop | continuation error). |
|
|
| ||
flag |
|
|
| |||||
|
|
| error | • Comes ON when the PLC No. 4 is during a stop error. |
|
|
|
11 - 44 | 11 - 44 |