11 TROUBLESHOOTING

MELSEC-Q

 

Error Code

Error Contents and Cause

Corrective Action

Corres-

 

ponding

 

(SD0)

1

 

 

 

CPU

 

 

 

 

 

 

 

 

• There was no response from the intelligent function module during

The CPU module is experiencing hardware problems. Contact your

QCPU

 

 

 

initial communication stage.

 

 

 

• The size of the buffer memory of the intelligent function module is

nearest Mitsubishi representative.

Rem

 

 

 

wrong.

 

 

 

1401

 

When parameter I/O allocation was being made, there was no

 

 

 

 

return signal from the special function module during initial

The special function module that was being accessed is

 

 

 

 

 

 

 

 

processing stage.

 

 

 

 

experiencing hardware problems. Contact your nearest Mitsubishi

QnA

 

 

 

When error is generated, the initial I/O number of the special

 

 

 

representative.

 

 

 

 

function module that corresponds to the common information is

 

 

 

 

 

 

 

 

 

stored.

 

 

 

 

 

The intelligent function module was accessed in the program, but

This suggests a CPU module hardware error. Contact your nearest

QCPU

 

 

 

there was no response.

Mitsubishi representative.

Rem

 

1402

 

 

 

 

 

 

The special function module was accessed during the execution of

The special function module that was being accessed is

 

 

 

 

a FROM/TO instruction set, but there was no response.

 

 

 

 

experiencing hardware problems. Contact your nearest Mitsubishi

QnA

 

 

 

When an error is generated, the program error location

 

 

 

representative.

 

 

 

 

corresponding to the individual information is stored.

 

 

 

 

 

 

 

 

 

• There was no response from the intelligent function module when

The intelligent function module that was being accessed is

QCPU

 

1403

 

the END instruction is executed.

experiencing hardware problems. Contact your nearest Mitsubishi

 

 

Rem

 

 

 

• An error is detected at the intelligent function module.

representative.

 

 

 

 

 

 

 

When performing a parameter I/O allocation a special function

 

 

 

1411

 

module could not be accessed during initial communications.

 

Rem

 

 

On error occurring, the head I/O number of the corresponding

A special function module, the CPU module, or the base unit is

 

 

 

 

 

 

special function module is stored in the common information.

 

 

 

 

experiencing problems. Contact your nearest Mitsubishi

 

 

 

 

The FROM/TO instruction set could not be executed, due to a

representative.

 

 

1412

 

system bus error with a special function module.

 

 

 

 

 

 

 

On error occurring, the program error location is stored in the

 

 

 

 

 

 

 

 

 

 

individual information.

 

 

 

 

 

 

(1) Change the High Performance model QCPU of function version

QCPU

 

 

 

 

A for the High Performance model QCPU of function version B.

 

 

 

The High Performance model QCPU of function version A was

function

 

 

 

(2) An intelligent function module, CPU module or the base unit is

 

 

 

loaded in a multiple CPU system configuration.

Ver. B

 

1413

 

experiencing problems. Contact your nearest Mitsubishi

 

 

 

or later

 

 

 

representative.

 

 

 

 

 

 

 

 

An error is detected on the system bus.

An intelligent function module, the CPU module, or the base unit is

QCPU

 

 

 

experiencing problems. Contact your nearest Mitsubishi

 

 

 

Wait-length time-out, arbitration time-out.

Rem

 

 

 

representative.

 

 

 

 

 

 

 

 

Fault of the loaded module was detected.

(1) Change the High Performance model QCPU of function version

QCPU

 

 

 

A for the High Performance model QCPU of function version B.

 

 

 

function

 

 

 

The High Performance model QCPU of function version A was

(2) An intelligent function module, CPU module or the base unit is

 

 

 

Ver. B

 

 

 

loaded in a multiple CPU system configuration.

experiencing problems. Contact your nearest Mitsubishi

 

1414

 

or later

 

 

 

representative.

 

 

 

 

 

 

 

 

An error is detected on the system bus.

An intelligent function module, the CPU module, or the base unit is

QCPU

 

 

 

experiencing problems. Contact your nearest Mitsubishi

 

 

 

Rem

 

 

 

 

representative.

 

 

 

 

 

 

1415

 

Fault of the main or extension base unit was detected.

An intelligent function module, CPU module or the base unit is

QCPU

 

 

function

 

 

 

 

experiencing problems. Contact your nearest Mitsubishi

 

 

 

 

Ver. B

 

1416

 

System bus fault was detected at PLC power-on or CPU module

representative.

 

 

reset.

or later

 

 

 

 

 

1421

 

Hardware fault at the system management module AS92R.

This is experiencing hardware problems.

Q4AR

 

 

Contact your nearest Mitsubishi representative.

 

 

 

 

 

 

1500

 

A momentary power supply interruption has occurred.

Check the power supply.

 

 

 

The power supply went off.

Rem

 

 

 

 

 

1510

 

The 5 VDC supplied to one of the two power-supply modules in the

 

 

 

 

redundant system extension base unit has dropped below 85% of

Check the supply voltage of the power supply module. If the voltage

 

 

 

 

the rated voltage.

 

 

 

 

is abnormal then replace the power supply module.

Q4AR

 

1520

 

The 5 VDC supplied to the power-supply modules in the extension

 

 

 

 

 

base unit has dropped below 80% of the rated voltage.

 

 

 

 

 

 

 

 

1530

 

The 24 VDC power supplied to the system management module

Check the power supply.

 

 

 

AS92R has dropped below 85% of the rated voltage.

 

 

 

 

 

 

 

1600

 

(1) Voltage in the CPU module battery.

(1) Change the battery.

 

 

 

(2) If the battery is for program memory, standard RAM or for the

 

 

 

(2) The CPU module battery is not connected.

 

 

 

 

back-up power function, install a lead connector.

 

 

 

 

 

 

 

 

 

 

 

 

 

1601

 

Voltage of the battery on memory card 1 has dropped below

Change the battery.

 

 

 

stipulated level.

 

 

 

 

 

 

 

1602

 

Voltage of the battery on memory card 2 has dropped below

Change the battery.

QnA

 

 

stipulated level.

 

 

 

 

 

 

 

 

 

Read the error common information at the peripheral device, and

 

 

 

 

I/O module information power ON is changed.

check and/or change the module that corresponds to the numerical

 

 

 

 

value (module number) there.

 

 

 

 

I/O module (or special function module) not installed properly or

Rem

 

 

 

Alternatively, monitor the special registers SD1400 to SD1431 at a

 

 

 

installed on the base unit.

 

2000

 

peripheral device, and change the fuse at the output module whose

 

 

 

 

 

 

 

 

bit has a value of "1".

 

 

 

 

 

 

 

 

 

The High Performance model QCPU of function version A was

Change the High Performance model QCPU of function version A

QCPU

 

 

 

function

 

 

 

loaded in a multiple CPU system configuration.

for the High Performance model QCPU of function version B.

Ver. B

 

 

 

 

 

or later

1 Characters in parentheses ( ) indicate the special register numbers where individual information is being stored.

11 - 22