9 LOADING AND INSTALLATION

MELSEC-Q

9 LOADING AND INSTALLATION

In order to increase the reliability of the system and exploit the maximum performance of its functions, this section describes the methods and precautions for the mounting and installation of the system.

9.1 General Safety Requirements

! DANGER

Install a safety circuit external to the PLC that keeps the entire

 

system safe even when there are problems with the external power

 

supply or the PLC module. Otherwise, trouble could result from

 

erroneous output or erroneous operation.

(1)Outside the PLC, construct mechanical damage preventing interlock circuits such as emergency stop, protective circuits, positioning upper and lower limits switches and interlocking forward/reverse operations.

(2)When the PLC detects the following problems, it will stop calculation and turn off all output in the case of (a).

In the case of (b), it will stop calculation and hold or turn off all output according to the parameter setting.

Note that the A1S series module will turn off the output in either of cases (a) and (b).

All outputs of AnS Series Module will be switched off in the following cases:

(a)The power supply module has over current protection equipment and over voltage protection equipment.

(b)The PLC CPUs self-diagnosis functions, such as the watch

dog timer error, detect problems.

In addition, all output will be turned on when there are problems that the PLC CPU cannot detect, such as in the I/O controller.

(3)Output could be left on or off when there is trouble in the outputs module relay or transistor. So build an external monitoring circuit that will monitor any single outputs that could cause serious trouble.

 

When overcurrent which exceeds the rating or caused by short-

 

circuited load flows in the output module for a long time, it may

 

cause smoke or fire. To prevent this, configure an external safety

 

circuit, such as fuse.

 

Build a circuit that turns on the external power supply when the PLC

 

main module power is turned on. If the external power supply is

 

9

turned on first, it could result in erroneous output or erroneous

operation.

 

When there are communication problems with the data link, refer to

 

the corresponding data link manual for the operating status of each

 

station. Not doing so could result in erroneous output or erroneous

 

operation.operating status of each station. Not doing so could result

 

in erroneous output or erroneous operation.

9 - 1

9 - 1