11 TROUBLESHOOTING
Special Register List
(4) Scan information
|
|
|
| Set by | Corresponding | Corresponding | |
Number | Name | Meaning | Explanation | ACPU | |||
(When set) | CPU | ||||||
|
|
|
| D9 | |||
|
|
|
|
|
| ||
| Execution | Execution type of | • Program number of program currently being executed is | S (Status |
|
| |
SD500 | program being | New |
| ||||
program No. | stored as BIN value. | change) |
| ||||
| executed |
|
| ||||
|
|
|
|
|
| ||
| Low speed | File name of low | • Program number of low speed program currently being | S (Every |
|
| |
SD510 | speed execution in | executed is stored as BIN value. | END | New |
| ||
program No. |
| ||||||
| progress | • Enabled only when SM510 is ON. | processing) |
|
| ||
|
|
|
| ||||
|
| Current scan time | • Current scan time is stored into SD520, SD521. | S (Every | D9017 format |
| |
SD520 |
| (Measurement is made in 100∝s increments.) | END |
| |||
| (ms unit) | change |
| ||||
|
| SD520: Place of ms is stored (storage range: 0 to 65535) | processing) |
| |||
|
|
|
|
| |||
| Current scan |
| SD521: Place of ∝s is stored (storage range: 0 to 900) |
|
|
| |
| time | Current scan time | Example: Current scan time 23.6ms is stored as indicated | S (Every |
|
| |
SD521 |
| below. | END | New |
| ||
| (∝s unit) |
| |||||
|
| SD520 = 23 | processing) |
|
| ||
|
|
|
|
| |||
|
|
| SD521 = 600 |
|
|
| |
SD522 |
| Initial scan time | • Scan time of initial execution program is stored into SD522, | S (First |
|
| |
Initial scan | (ms unit) | SD523. (Measurement is made in 100∝s increments.) |
|
| |||
| END | New |
| ||||
| time | Initial scan time | SD522: Place of ms is stored (storage range: 0 to 65535) |
| |||
SD523 | processing) |
|
| ||||
| (∝s unit) | SD523: Place of ∝s is stored (storage range: 0 to 900) |
|
| |||
|
|
|
|
| |||
|
| Minimum scan time | • Minimum value of scan time with the exception of initial | S (Every | D9018 format |
| |
SD524 |
| END |
| ||||
| (ms unit) | execution program scan time is stored into SD524, SD525. | change |
| |||
| Minimum scan | processing) |
| ||||
| time |
| (Measurement is made in 100∝s increments.) |
|
|
| |
|
| S (Every |
|
| |||
| Minimum scan time | SD524: Place of ms is stored (storage range: 0 to 65535) |
|
| |||
SD525 |
| END | New |
| |||
| (∝s unit) | SD525: Place of ∝s is stored (storage range: 0 to 900) |
| ||||
|
| processing) |
|
| |||
|
|
|
|
|
| ||
SD526 |
| Maximum scan time | • Maximum value of scan time with the exception of initial |
| D9019 format |
| |
| (ms unit) | execution program scan time is stored into SD526, SD527. | S (Every | change |
| ||
| Maximum scan |
| |||||
|
| (Measurement is made in 100∝s increments.) | END |
|
| ||
| time | Maximum scan time |
|
| |||
SD527 | SD526: Place of ms is stored (storage range: 0 to 65535) | processing) | New |
| |||
| (∝s unit) |
| |||||
|
| SD527: Place of ∝s is stored (storage range: 0 to 900) |
|
|
| ||
|
|
|
|
|
| ||
SD528 | Current scan | Current scan time | • Current scan time of low speed program is stored into |
|
|
| |
time | (ms unit) | SD528, SD529. (Measurement is made in 100∝s | S (Every |
|
| ||
|
|
| |||||
| for low speed | Current scan time | increments.) | END | New |
| |
SD529 | execution type | SD528: Place of ms is stored (storage range: 0 to 65535) | processing) |
|
| ||
| programs | (∝s unit) | SD529: Place of ∝s is stored (storage range: 0 to 900) |
|
|
| |
|
|
|
|
| |||
SD532 | Minimum scan | Minimum scan time | • Minimum value of low speed program scan time is stored |
|
|
| |
time for | (ms unit) | into SD532, SD533. (Measurement is made in 100∝s | S (Every |
|
| ||
|
|
| |||||
| low speed | Minimum scan time | increments.) | END | New |
| |
SD533 | execution type | (∝s unit) | SD532: Place of ms is stored (storage range: 0 to 65535) | processing) |
|
| |
| programs |
| SD533: Place of ∝s is stored (storage range: 0 to 900) |
|
|
| |
SD534 | Maximum scan | Maximum scan time | • Maximum value of low speed program scan time with the |
|
|
| |
time for | (ms unit) | exception of the first scan is stored into SD534, SD535. | S (Every |
|
| ||
|
|
| |||||
| low speed | Maximum scan time | (Measurement is made in 100∝s increments.) | END | New |
| |
SD535 | execution type | SD534: Place of ms is stored (storage range: 0 to 65535) | processing) |
|
| ||
| programs | (∝s unit) | SD535: Place of ∝s is stored (storage range: 0 to 900) |
|
|
| |
|
|
|
|
| |||
SD540 |
| END processing time | • Time from scan program end until next scan start is stored |
|
|
| |
END | (ms unit) | into SD540, SD541. (Measurement is made in 100∝s | S (Every |
|
| ||
|
|
| |||||
| processing | END processing time | increments.) | END | New |
| |
SD541 | time | SD540: Place of ms is stored (storage range: 0 to 65535) | processing) |
|
| ||
(∝s unit) |
|
| |||||
|
| SD541: Place of ∝s is stored (storage range: 0 to 900) |
|
|
| ||
|
|
|
|
|
|
11 - 78 | 11 - 78 |