11 TROUBLESHOOTING

11.2.11 Flowchart for when output module LED is not turned on

MELSEC-Q

The following shows the flowchart to be followed when the output module LED does not turn on during PLC operation.

Output module LED not turned on

 

 

NO (Flickering)

 

 

 

Is the "MODE" LED on?

 

 

 

 

 

Refer to Section 11.2.3.

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Is the LED on when it is

 

 

NO

 

 

 

 

 

Reexamine the program.

 

 

 

 

monitored on GX Developer?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check the input/output number on the GX Developer system monitor.

Does the output number match?

NO

 

 

YES

 

 

 

 

 

 

Is the LED turned on

NO

when another output module

 

is forcibly turned on?

 

 

YES

 

 

 

 

 

 

Is the LED turned

on when the output module is NO changed for another output module,

which is then forcibly

turned on?

YES

Output module hardware fault. Please consult your local Mitsubishi service center or representative, explaining a detailed description of the problem.

Change the output number.

CPU module, base unit, extension Outputcable hardwaremodule hfardwareult. fault PleaseCon ultconsultyour localyoursystemlocal Mitsubishiservice, agenservicey centerorbranchor representative,office. explaining a detailed description of the problem.

11 - 10

11 - 10