11 TROUBLESHOOTING
| Error Code |
| Error Contents and Cause | Corrective Action |
|
| Corres- | |
|
|
|
| ponding | ||||
| (SD0) | 1 |
|
|
| |||
|
|
|
|
|
| CPU | ||
|
|
|
|
|
|
|
| |
|
|
|
| Program memory capacity was exceeded by performing boot | (1) Check and correct the parameters (boot setting). | QCPU | ||
|
|
|
| (2) Delete unnecessary files in the program memory. | function | |||
|
|
|
| operation or automatic write to standard ROM. | (3) Choose "Clear program memory" for boot in the parameter so | Ver. B | ||
| 2401 |
|
|
| that boot is started after the program memory is cleared. | or later | ||
|
|
| The file designated at the parameter PLC RAS settings fault history | Read the error individual information at the peripheral device, check |
| |||
|
|
|
|
| ||||
|
|
|
| to be sure that the parameter drive name and file name correspond |
| |||
|
|
|
| area has not been created. | to the numerical values there (parameter number), and correct. |
| ||
|
|
|
|
| Check the space remaining in the memory card. |
| ||
|
|
|
|
| Read the error individual information at the peripheral device, check |
| ||
| 2410 |
|
| The file designated by the sequence program cannot be found. | to be sure that the program corresponds to the numerical values |
| ||
|
|
| there (program location), and correct. |
|
|
| ||
|
|
|
|
| Create a file created using parameters, and load it to the CPU |
| ||
|
|
|
|
| module. |
|
|
|
| 2411 |
|
| The sequence program designated a file that cannot be designated | Read the error individual information at the peripheral device, check |
| ||
|
|
| by the sequence program (comment file, etc.). |
| ||||
|
|
|
| to be sure that the program corresponds to the numerical values |
| |||
| 2412 |
|
| The SFC program file is one that cannot be designated by the | there (program location), and correct. |
|
|
|
|
|
| sequence program. |
|
|
| ||
|
|
|
|
|
|
|
| |
|
|
|
| No data has been written to the file designated by the sequence | Read the error individual information at the peripheral device, check |
| ||
| 2413 |
|
| to be sure that the program corresponds to the numerical values |
| |||
|
|
| program. | there (program location), and correct. |
|
|
| |
|
|
|
|
|
|
| ||
|
|
|
|
| Check to ensure that the designated file has not been write protected. |
| ||
|
|
|
| There is a program file that uses a device that exceeds the device | Read the error common information at the peripheral device, check |
| ||
| 2500 |
|
| to be sure that the parameter device allocation setting and the |
| |||
|
|
| allocation range designated by the parameter device settings. | program file device allocation correspond to the numerical values |
| |||
|
|
|
|
| ||||
|
|
|
|
| there (file name), and correct if necessary. |
|
|
|
| 2501 |
|
| There are multiple program files although "none" has been set at | Edit the parameter program setting to "yes". |
|
|
|
|
|
| the parameter program settings. | Alternatively, delete unneeded programs. |
|
|
| |
|
|
|
|
|
|
| ||
| 2502 |
|
| The program file is incorrect. | Check whether the program version is | .QPG, and check the |
| |
|
|
| Alternatively, the file contents are not those of a sequence program. | file contents to be sure they are for a sequence program. |
| |||
|
|
|
|
| ||||
| 2503 |
|
| There are no program files at all. | Check program configuration. |
|
|
|
2504 |
|
| Two or more SFC normal programs or control programs have been | Check parameters and program configuration. |
|
|
| |
|
| designated. |
|
|
| |||
|
|
|
|
|
|
|
| |
|
|
|
| In a multiple CPU system, the intelligent function module under | (1) Specify the first I/O number of the intelligent function module | QCPU | ||
|
|
|
| function | ||||
|
|
|
| control of another station is specified in the interrupt pointer setting | under control of the host station. |
|
| |
|
|
|
|
|
| Ver. B | ||
|
|
|
| of the parameter. | (2) Delete the interrupt pointer setting of the parameter. | |||
3000 |
|
| or later | |||||
|
|
|
|
|
| |||
|
| The parameter settings for timer time limit setting, the | (1) Read the error detailed information at the peripheral device, |
| ||||
|
|
|
|
| ||||
|
|
|
| contact, the common pointer number, the general data processing, |
| |||
|
|
|
| check the parameter items corresponding to the numerical |
| |||
|
|
|
| number of vacant slots, or system interrupt settings are outside the | Rem | |||
|
|
|
| values (parameter numbers) there, and correct when necessary. | ||||
|
|
|
| range that can be used by the CPU module. | ||||
|
|
|
| (2) If the error is still generated following the correction of the |
| |||
| 3001 |
|
| Parameter contents have been destroyed. |
| |||
|
| parameter settings, it is likely that there is a memory error, either |
|
| ||||
3002 |
|
| When "use the following files" is selected for the file registers in the | in the internal CPU RAM/program memory or on the memory |
| |||
|
| PLC file setting parameter, the specified file does not exist though | card. Contact your nearest Mitsubishi representative. |
| ||||
|
|
|
| the file register capacity has been set. |
|
|
|
|
|
|
|
| The automatic refresh range of the multiple CPU system exceeded | Change the file register file for the one | QCPU | ||
|
|
|
| function | ||||
|
|
|
| the file register capacity. | range. |
|
| Ver. B |
|
|
|
|
|
|
|
| or later |
3003 |
|
|
| (1) Read the error detailed information at the peripheral device, |
| |||
|
|
| check the parameter items corresponding to the numerical |
| ||||
|
|
|
| The number of devices set at the parameter device settings | values (parameter numbers) there, and correct when necessary. |
| ||
|
|
|
| (2) If the error is still generated following the correction of the |
| |||
|
|
|
| exceeds the possible CPU module range. |
| |||
|
|
|
| parameter settings, it is likely that there is a memory error, either |
| |||
|
|
|
|
|
| |||
|
|
|
|
| in the internal CPU RAM/program memory or on the memory |
| ||
|
|
|
|
| card. Contact your nearest Mitsubishi representative. |
| ||
3004 |
|
| The parameter file is incorrect. | Check whether the parameter file version is | .QPA, and |
| ||
|
| Alternatively, the contents of the file are not parameters. | check the file contents to be sure they are parameters. |
| ||||
|
|
|
|
| ||||
|
|
|
|
| (1) Delete the setting of the Q02CPU’s high speed interrupt |
| ||
|
|
|
|
| parameter. To use high speed interrupts, change the CPU |
| ||
|
|
|
| (1) The high speed interrupt parameter is set in a Q02CPU. | module to one of the Q02H/Q06H/Q12H/Q25HCPU. | QCPU | ||
|
|
|
| (2) To use a multiple CPU system, delete the setting of the high- | ||||
|
|
|
| (2) The high speed parameter is set in a multiple CPU system. | speed interrupt parameter. To use high speed interrupts, change | serial | ||
|
|
|
| (3) The high speed interrupt parameter is set when a QA1S B or | ||||
3006 |
|
| the system to a single PLC system. |
|
| No. | ||
|
| QA B is used. |
|
| ||||
|
|
|
| (3) To use either the QA1S B or QA B, delete the setting of the | 04012 | |||
|
|
|
| (4) No module is installed at the I/O address designated by the high | ||||
|
|
|
| high speed interrupt parameter. To use high speed interrupts, do | or later | |||
|
|
|
| speed interrupt parameter. | ||||
|
|
|
| not use the QA1S B/QA B. |
|
| ||
|
|
|
|
| (4) |
| ||
|
|
|
|
| interrupt parameter. |
|
|
|
3009 |
|
| A modules are set to control PLCs in a multiple CPU system. |
| ||||
|
| QCPU. (Change the parameters of all stations in the multiple CPU |
| |||||
|
|
|
|
| system.) |
|
|
|
3010 |
|
| The | Match (preset count of multiple PLC setting) - (CPU (empty) setting |
| |||
|
| number in a multiple CPU system. | in I/O assignment) with the actual number of CPUs loaded. |
| ||||
|
|
|
| QCPU | ||||
3012 |
|
| Multiple CPU setting or control PLC setting differs from that of the | Match the multiple PLC setting or control CPU setting in the | ||||
|
| reference station in a multiple CPU system. | parameter with that of the reference station (station 1). | function | ||||
|
|
|
| |||||
|
|
|
|
|
|
|
| Ver. B |
|
|
|
| Multiple CPU automatic refresh setting is any of the followings in a | Check the following in the multiple CPU automatic refresh | |||
|
|
|
| or later | ||||
|
|
|
| multiple CPU system. | ||||
|
|
|
| parameters and make correction. |
|
|
| |
|
|
|
| (1) When a bit device is specified as a refresh device, a number |
|
|
| |
3013 |
|
| (1) When specifying the bit device, specify a multiple of 16 for the |
| ||||
|
| other than a multiple of 16 is specified for the |
| |||||
|
|
|
| device. | refresh starting device. |
|
|
|
|
|
|
| (2) The device specified is other than the one that may be specified. | (2) Specify the device that may be specified for the refresh device. |
| ||
|
|
|
| (3) Set the number of send points to an even number. |
| |||
|
|
|
| (3) The number of send points is an odd number. |
| |||
|
|
|
|
|
|
|
|
1 Characters in parentheses ( ) indicate the special register numbers where individual information is being stored.
11 - 28 | 11 - 28 |