11 TROUBLESHOOTING

MELSEC-Q

 

Error Code

 

Error Contents and Cause

Corrective Action

 

 

Corres-

 

 

 

 

ponding

 

(SD0)

1

 

 

 

 

 

 

 

 

 

CPU

 

 

 

 

 

 

 

 

 

 

 

 

Program memory capacity was exceeded by performing boot

(1) Check and correct the parameters (boot setting).

QCPU

 

 

 

 

(2) Delete unnecessary files in the program memory.

function

 

 

 

 

operation or automatic write to standard ROM.

(3) Choose "Clear program memory" for boot in the parameter so

Ver. B

 

2401

 

 

 

that boot is started after the program memory is cleared.

or later

 

 

 

The file designated at the parameter PLC RAS settings fault history

Read the error individual information at the peripheral device, check

 

 

 

 

 

 

 

 

 

 

to be sure that the parameter drive name and file name correspond

 

 

 

 

 

area has not been created.

to the numerical values there (parameter number), and correct.

 

 

 

 

 

 

Check the space remaining in the memory card.

 

 

 

 

 

 

Read the error individual information at the peripheral device, check

 

 

2410

 

 

The file designated by the sequence program cannot be found.

to be sure that the program corresponds to the numerical values

 

 

 

 

there (program location), and correct.

 

 

 

 

 

 

 

 

Create a file created using parameters, and load it to the CPU

 

 

 

 

 

 

module.

 

 

 

 

2411

 

 

The sequence program designated a file that cannot be designated

Read the error individual information at the peripheral device, check

 

 

 

 

by the sequence program (comment file, etc.).

 

 

 

 

 

to be sure that the program corresponds to the numerical values

 

 

2412

 

 

The SFC program file is one that cannot be designated by the

there (program location), and correct.

 

 

 

 

 

 

sequence program.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No data has been written to the file designated by the sequence

Read the error individual information at the peripheral device, check

 

 

2413

 

 

to be sure that the program corresponds to the numerical values

 

 

 

 

program.

there (program location), and correct.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check to ensure that the designated file has not been write protected.

 

 

 

 

 

There is a program file that uses a device that exceeds the device

Read the error common information at the peripheral device, check

 

 

2500

 

 

to be sure that the parameter device allocation setting and the

 

 

 

 

allocation range designated by the parameter device settings.

program file device allocation correspond to the numerical values

 

 

 

 

 

 

 

 

 

 

 

there (file name), and correct if necessary.

 

 

 

 

2501

 

 

There are multiple program files although "none" has been set at

Edit the parameter program setting to "yes".

 

 

 

 

 

 

the parameter program settings.

Alternatively, delete unneeded programs.

 

 

 

 

 

 

 

 

 

 

 

2502

 

 

The program file is incorrect.

Check whether the program version is

.QPG, and check the

 

 

 

 

Alternatively, the file contents are not those of a sequence program.

file contents to be sure they are for a sequence program.

 

 

 

 

 

 

 

2503

 

 

There are no program files at all.

Check program configuration.

 

 

 

2504

 

 

Two or more SFC normal programs or control programs have been

Check parameters and program configuration.

 

 

 

 

 

designated.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

In a multiple CPU system, the intelligent function module under

(1) Specify the first I/O number of the intelligent function module

QCPU

 

 

 

 

function

 

 

 

 

control of another station is specified in the interrupt pointer setting

under control of the host station.

 

 

 

 

 

 

 

 

Ver. B

 

 

 

 

of the parameter.

(2) Delete the interrupt pointer setting of the parameter.

3000

 

 

or later

 

 

 

 

 

 

 

 

The parameter settings for timer time limit setting, the RUN-PAUSE

(1) Read the error detailed information at the peripheral device,

 

 

 

 

 

 

 

 

 

 

contact, the common pointer number, the general data processing,

 

 

 

 

 

check the parameter items corresponding to the numerical

 

 

 

 

 

number of vacant slots, or system interrupt settings are outside the

Rem

 

 

 

 

values (parameter numbers) there, and correct when necessary.

 

 

 

 

range that can be used by the CPU module.

 

 

 

 

(2) If the error is still generated following the correction of the

 

 

3001

 

 

Parameter contents have been destroyed.

 

 

 

parameter settings, it is likely that there is a memory error, either

 

 

3002

 

 

When "use the following files" is selected for the file registers in the

in the internal CPU RAM/program memory or on the memory

 

 

 

PLC file setting parameter, the specified file does not exist though

card. Contact your nearest Mitsubishi representative.

 

 

 

 

 

the file register capacity has been set.

 

 

 

 

 

 

 

 

The automatic refresh range of the multiple CPU system exceeded

Change the file register file for the one refresh-enabled in the whole

QCPU

 

 

 

 

function

 

 

 

 

the file register capacity.

range.

 

 

Ver. B

 

 

 

 

 

 

 

 

or later

3003

 

 

 

(1) Read the error detailed information at the peripheral device,

 

 

 

 

check the parameter items corresponding to the numerical

 

 

 

 

 

The number of devices set at the parameter device settings

values (parameter numbers) there, and correct when necessary.

 

 

 

 

 

(2) If the error is still generated following the correction of the

 

 

 

 

 

exceeds the possible CPU module range.

 

 

 

 

 

parameter settings, it is likely that there is a memory error, either

 

 

 

 

 

 

 

 

 

 

 

 

in the internal CPU RAM/program memory or on the memory

 

 

 

 

 

 

card. Contact your nearest Mitsubishi representative.

 

3004

 

 

The parameter file is incorrect.

Check whether the parameter file version is

.QPA, and

 

 

 

Alternatively, the contents of the file are not parameters.

check the file contents to be sure they are parameters.

 

 

 

 

 

 

 

 

 

 

 

(1) Delete the setting of the Q02CPU’s high speed interrupt

 

 

 

 

 

 

parameter. To use high speed interrupts, change the CPU

 

 

 

 

 

(1) The high speed interrupt parameter is set in a Q02CPU.

module to one of the Q02H/Q06H/Q12H/Q25HCPU.

QCPU

 

 

 

 

(2) To use a multiple CPU system, delete the setting of the high-

 

 

 

 

(2) The high speed parameter is set in a multiple CPU system.

speed interrupt parameter. To use high speed interrupts, change

serial

 

 

 

 

(3) The high speed interrupt parameter is set when a QA1S B or

3006

 

 

the system to a single PLC system.

 

 

No.

 

 

QA B is used.

 

 

 

 

 

 

(3) To use either the QA1S B or QA B, delete the setting of the

04012

 

 

 

 

(4) No module is installed at the I/O address designated by the high

 

 

 

 

high speed interrupt parameter. To use high speed interrupts, do

or later

 

 

 

 

speed interrupt parameter.

 

 

 

 

not use the QA1S B/QA B.

 

 

 

 

 

 

 

(4) Re-examine the I/O address designated by the high speed

 

 

 

 

 

 

interrupt parameter.

 

 

 

3009

 

 

A modules are set to control PLCs in a multiple CPU system.

Re-set the parameter I/O assignment to control them under one

 

 

 

QCPU. (Change the parameters of all stations in the multiple CPU

 

 

 

 

 

 

system.)

 

 

 

3010

 

 

The parameter-set number of CPU modules differs from the actual

Match (preset count of multiple PLC setting) - (CPU (empty) setting

 

 

 

number in a multiple CPU system.

in I/O assignment) with the actual number of CPUs loaded.

 

 

 

 

 

QCPU

3012

 

 

Multiple CPU setting or control PLC setting differs from that of the

Match the multiple PLC setting or control CPU setting in the

 

 

reference station in a multiple CPU system.

parameter with that of the reference station (station 1).

function

 

 

 

 

 

 

 

 

 

 

 

 

Ver. B

 

 

 

 

Multiple CPU automatic refresh setting is any of the followings in a

Check the following in the multiple CPU automatic refresh

 

 

 

 

or later

 

 

 

 

multiple CPU system.

 

 

 

 

parameters and make correction.

 

 

 

 

 

 

 

(1) When a bit device is specified as a refresh device, a number

 

 

 

3013

 

 

(1) When specifying the bit device, specify a multiple of 16 for the

 

 

 

other than a multiple of 16 is specified for the refresh-starting

 

 

 

 

 

device.

refresh starting device.

 

 

 

 

 

 

 

(2) The device specified is other than the one that may be specified.

(2) Specify the device that may be specified for the refresh device.

 

 

 

 

 

(3) Set the number of send points to an even number.

 

 

 

 

 

(3) The number of send points is an odd number.

 

 

 

 

 

 

 

 

 

1 Characters in parentheses ( ) indicate the special register numbers where individual information is being stored.

11 - 28

11 - 28