9 LOADING AND INSTALLATION
(b) In case of slim type main base unit
Indicates the panel top, wiring duct or any part position.
30 mm
(1.18 inch) or more 1
Panel
30 mm
(1.18 inch) or more
17 mm (0.67 inch) or more 2 | 5 mm (0.20 inch) or more |
PLC
Door
20 mm (0.79 inch) or more 3
1 : For wiring duct with 50 (1.97 inch) mm or less height. 40 mm (1.58 inch) or more for other cases.
2 : The cable of the power supply module of the slim type main base unit protrudes out of the left end of the module. Install the module while reserving 17 mm (0.67 inch) or more wiring space. If the cable sheath is susceptible to damage caused by a structural object or part on the left side of the module, take a protective measure with spiral tube or a similar insulator.
3 : 80 mm (3.15 inch) mm or more for the connector type.
9 - 13 | 9 - 13 |