5 - 2

5 POWER SUPPLY MODULE

MELSEC-Q

 

 

 

 

 

 

Power Supply Module Specifications (Continued)

 

 

 

 

 

 

 

 

 

 

Item

 

 

 

Performance Specifications

 

 

 

 

 

Q64P

 

 

 

 

 

 

 

 

 

Base loading position

Power supply module loading slot

 

 

Applicable base unit

 

Q3†B, Q6†B

 

 

 

 

 

 

 

+10%

 

 

Input power supply

 

100 to 120VAC/200 to 240VAC -15%

 

 

 

 

 

 

 

(85V to 132VAC/170 to 264VAC)

 

 

Input frequency

 

50/60Hz ±5%

 

 

Input voltage distortion factor

Within 5% (refer to section 5.1.3)

 

 

Max. input apparent power

160VA

 

 

Inrush current

 

20A within 8ms

 

 

Rated output

 

 

5VDC

8.5A

 

 

current

 

 

24VDC

——

 

 

Overcurrent

 

 

5VDC

9.9A or more

 

 

protection*1

 

 

24VDC

——

 

 

Overvoltage

 

 

5VDC

5.5 to 6.5V

 

 

protection*2

 

 

24VDC

——

 

 

Efficiency

 

 

 

70% or more

5

 

Allowable momentary power failure

Within 20ms

 

period*3

 

 

 

 

 

 

 

 

 

Dielectric withstand voltage

Across inputs/LG and outputs/FG

 

 

 

 

2830VAC rms/3 cycles (2000 m (6562 ft.))

 

 

 

 

 

 

 

 

 

Insulation resistance

Across inputs and outputs (LG and FG separated), across inputs and LG/FG, across outputs

 

 

and FG/LG 10M or more by insulation resistance tester

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• By noise simulator of 1500Vp-p noise voltage, 1 s noise width and 25 to 60Hz noise

 

 

Noise durability

 

frequency

 

 

 

 

 

 

 

• Noise voltage IEC61000-4-4, 2kV

 

 

Operation indication

 

LED indication (lit at 5VDC output)

 

 

Fuse

 

 

 

Built-in (Unchangeable by user)

 

 

 

 

Application

ERR contact (contact switched off (opened: normally closed contact) at an error stop of CPU

 

 

 

 

module), for CPU module operating status output

 

 

 

 

 

 

 

 

 

 

 

Rated switching voltage,

24VDC, 0.5A

 

 

 

 

current

 

 

 

Contact

 

 

 

 

 

 

Minimum switching load

5VDC, 1mA

 

 

output

 

 

 

 

Response time

OFF to ON: 10ms max. ON to OFF: 12ms max.

 

 

section

 

 

 

 

Life

 

Mechanical : More than 2 million times

 

 

 

 

 

 

 

 

 

 

Electrical : More than 100 thousand times at rated switching voltage, current

 

 

 

 

 

 

 

 

 

 

 

Surge suppressor

No

 

 

 

 

Fuse

 

No

 

 

Terminal screw size

 

M3.5 × 7

 

 

Applicable wire size

 

0.75 to 2mm2

 

 

Applicable solderless terminal

RAV1.25 to 3.5, RAV2 to 3.5

 

 

Applicable tightening torque

66 to 89N•cm

 

 

External

 

 

H

98mm (3.86inch)

 

 

 

 

W

55.2mm (2.33inch)

 

 

dimensions

 

 

 

 

 

 

D

115mm (4.53inch)

 

 

 

 

 

 

 

 

Weight

 

 

 

0.40kg

5 - 2