5 POWER SUPPLY MODULE
|
|
|
|
|
| Power Supply Module Specifications (Continued) | |
|
|
|
|
|
|
|
|
|
| Item |
|
|
| Performance Specifications | |
|
|
|
|
| Q64P | ||
|
|
|
|
|
|
| |
|
| Base loading position | Power supply module loading slot | ||||
|
| Applicable base unit |
| Q3B, Q6B | |||
|
|
|
|
|
|
| +10% |
|
| Input power supply |
| 100 to 120VAC/200 to 240VAC | |||
|
|
|
|
|
|
| (85V to 132VAC/170 to 264VAC) |
|
| Input frequency |
| 50/60Hz ±5% | |||
|
| Input voltage distortion factor | Within 5% (refer to section 5.1.3) | ||||
|
| Max. input apparent power | 160VA | ||||
|
| Inrush current |
| 20A within 8ms | |||
|
| Rated output |
|
| 5VDC | 8.5A | |
|
| current |
|
| 24VDC | ||
|
| Overcurrent |
|
| 5VDC | 9.9A or more | |
|
| protection*1 |
|
| 24VDC | ||
|
| Overvoltage |
|
| 5VDC | 5.5 to 6.5V | |
|
| protection*2 |
|
| 24VDC | ||
|
| Efficiency |
|
|
| 70% or more | |
5 |
| Allowable momentary power failure | Within 20ms | ||||
| period*3 |
|
|
| |||
|
|
|
|
| |||
| Dielectric withstand voltage | Across inputs/LG and outputs/FG | |||||
|
| ||||||
|
| 2830VAC rms/3 cycles (2000 m (6562 ft.)) | |||||
|
|
|
|
|
|
| |
|
| Insulation resistance | Across inputs and outputs (LG and FG separated), across inputs and LG/FG, across outputs | ||||
|
| and FG/LG 10M or more by insulation resistance tester | |||||
|
|
|
|
|
|
| |
|
|
|
|
|
|
| • By noise simulator of |
|
| Noise durability |
| frequency | |||
|
|
|
|
|
|
| • Noise voltage |
|
| Operation indication |
| LED indication (lit at 5VDC output) | |||
|
| Fuse |
|
|
| ||
|
|
|
| Application | ERR contact (contact switched off (opened: normally closed contact) at an error stop of CPU | ||
|
|
|
| module), for CPU module operating status output | |||
|
|
|
|
|
|
| |
|
|
|
| Rated switching voltage, | 24VDC, 0.5A | ||
|
|
|
| current |
| ||
|
| Contact |
|
|
| ||
|
|
| Minimum switching load | 5VDC, 1mA | |||
|
| output |
| ||||
|
|
| Response time | OFF to ON: 10ms max. ON to OFF: 12ms max. | |||
|
| section |
| ||||
|
|
| Life |
| Mechanical : More than 2 million times | ||
|
|
|
|
| |||
|
|
|
|
| Electrical : More than 100 thousand times at rated switching voltage, current | ||
|
|
|
|
|
|
| |
|
|
|
| Surge suppressor | No | ||
|
|
|
| Fuse |
| No | |
|
| Terminal screw size |
| M3.5 × 7 | |||
|
| Applicable wire size |
| 0.75 to 2mm2 | |||
|
| Applicable solderless terminal | RAV1.25 to 3.5, RAV2 to 3.5 | ||||
|
| Applicable tightening torque | 66 to 89N•cm | ||||
|
| External |
|
| H | 98mm (3.86inch) | |
|
|
|
| W | 55.2mm (2.33inch) | ||
|
| dimensions |
|
| |||
|
|
|
| D | 115mm (4.53inch) | ||
|
|
|
|
|
| ||
|
| Weight |
|
|
| 0.40kg |
5 - 2