11 TROUBLESHOOTING

MELSEC-Q

Special Relay List

(3) System clocks/counters

Number

Name

 

 

 

 

 

 

 

 

Meaning

 

Explanation

Set by

Corresponding

Applicable

 

 

 

 

 

 

 

 

 

(When Set)

ACPU

CPU

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

M9

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SM400

Always ON

 

 

ON

 

 

 

 

 

 

 

 

 

 

• Normally is ON

S

M9036

 

 

 

 

 

 

 

 

 

 

 

 

 

(Every END

 

 

 

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

processing)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SM401

Always OFF

ON

 

 

 

 

 

 

 

 

 

 

 

 

S

 

 

 

 

 

 

 

• Normally is OFF

(Every END

M9037

 

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

processing)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ON for 1 scan

ON

1 scan

• After RUN, ON for 1 scan only.

S

 

 

SM402

• This connection can be used for scan execution type

(Every END

M9038

 

only after RUN

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

programs only.

processing)

 

 

 

After RUN, OFF

ON

 

 

 

 

 

 

 

 

• After RUN, OFF for 1 scan only.

S

 

 

SM403

 

 

1 scan

• This connection can be used for scan execution type

(Every END

M9039

 

 

for 1 scan only

OFF

 

 

 

 

 

programs only.

processing)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Low speed

 

 

 

 

 

 

 

 

 

 

 

 

 

• After RUN, ON for 1 scan only.

S

 

 

 

execution type

 

ON

1 scan

 

 

SM404

program

 

• This connection can be used for low speed execution

(Every END

New

 

 

OFF

 

 

 

 

 

 

 

ON for 1 scan

 

 

 

 

 

 

 

 

type programs only.

processing)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

only after RUN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Low speed

 

 

 

 

 

 

 

 

 

 

 

 

 

• After RUN, OFF for 1 scan only.

S

 

 

 

execution type

ON

 

 

 

 

 

 

 

 

 

SM405

program

 

1 scan

• This connection can be used for low speed execution

(Every END

New

 

OFF

 

 

After RUN, OFF

 

 

 

 

 

type programs only.

processing)

 

 

 

for 1 scan only

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• Repeatedly changes between ON and OFF at 5-ms

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

interval.

 

 

 

SM409

0.01 second

 

 

0.005 sec.

 

 

 

 

 

• When PLC power supply is turned OFF or a CPU module

S (Status

New

QCPU

 

 

0.005 sec.

reset is performed, goes from OFF to start.

 

clock

 

 

 

 

 

 

 

 

 

 

 

 

 

• Note that the ON-OFF status changes when the

change)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

designated time has elapsed during the execution of the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

program.

 

 

 

SM410

0.1 second clock

 

0.05 sec.

0.05 sec.

• Repeatedly changes between ON and OFF at each

 

M9030

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

designated time interval.

 

 

 

 

 

 

 

0.1sec.

 

 

 

 

 

 

 

 

SM411

0.2 second clock

 

 

0.1sec.

• When PLC power supply is turned OFF or a CPU module

 

M9031

 

 

 

 

 

 

 

 

 

S (Status

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

reset is performed, goes from OFF to start.

 

 

 

 

 

0.5 sec.

 

 

 

 

 

change)

 

 

SM412

1 second clock

 

0.5 sec.

• Note that the ON-OFF status changes when the

M9032

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

designated time has elapsed during the execution of the

 

 

 

 

 

 

1 sec.

 

 

 

 

 

 

 

 

SM413

2 second clock

 

1 sec.

program.

 

M9033

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• Goes between ON and OFF in accordance with the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

number of seconds designated by SD414.

 

 

 

SM414

2n second clock

 

n sec.

 

 

 

 

 

• When PLC power supply is turned OFF or a CPU module

S (Status

M9034 format

 

 

n sec.

reset is performed, goes from OFF to start.

 

 

 

 

 

 

 

 

 

change)

change

 

 

 

 

 

 

 

 

 

 

 

• Note that the ON-OFF status changes when the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

designated time has elapsed during the execution of the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

program.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• Switches between ON and OFF in accordance with the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

number of milliseconds designated by SD415.

 

 

 

SM415

2n (ms) clock

n(ms)

 

 

 

 

 

• When PLC power supply is turned OFF or a CPU module

S (Status

New

QCPU

n(ms)

reset is performed, goes from OFF to start.

 

 

 

 

 

 

 

 

change)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• Note that the ON-OFF status changes when the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

designated time has elapsed during the execution of the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

program.

 

 

 

SM420

User timing clock

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

M9020

 

 

No.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SM421

User timing clock

 

 

 

 

 

 

 

 

 

 

 

 

 

• Relay repeats ON/OFF switching at fixed scan intervals.

 

M9021

 

 

No.1

 

 

 

 

 

 

 

 

 

 

 

 

 

• When PLC power supply is turned OFF or a CPU module

S

 

 

 

User timing clock

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SM422

 

 

 

 

 

 

 

 

 

 

 

 

 

reset is performed, goes from OFF to start.

(Every END

M9022

 

No.2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• The ON/OFF intervals are set with the DUTY instruction.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

processing)

 

 

 

User timing clock

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SM423

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DUTY

n1

n2

SM420

 

 

 

M9023

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No.3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SM424

User timing clock

 

 

n2

n2

 

 

 

 

 

 

 

 

M9024

 

No.4

 

 

scan

scan

 

 

 

 

 

 

 

 

 

 

SM430

User timing clock

 

 

 

 

 

 

 

 

n1

 

 

 

 

 

 

 

 

 

 

No.5

 

 

 

 

 

 

 

 

scan

 

 

 

 

 

 

 

 

 

 

SM431

User timing clock

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No.6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S

 

 

 

User timing clock

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SM432

 

 

 

 

 

 

 

 

 

 

 

 

 

• For use with SM420 to SM424 low speed programs.

(Every END

New

 

 

No.7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

processing)

 

 

SM433

User timing clock

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No.8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SM434

User timing clock

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No.9

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

11 - 47

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

11 - 47