9 LOADING AND INSTALLATION

9.3 Module Installation

9.3.1 Precaution on installation

MELSEC-Q

CAUTION

Use the PLC in an environment that meets the general specifications

 

contained in this manual. Using this PLC in an environment outside the

 

range of the general specifications could result in electric shock, fire,

 

erroneous operation, and damage to or deterioration of the product.

 

Hold down the module loading lever at the module bottom, and

 

securely insert the module fixing latch into the fixing hole in the base

 

unit. Incorrect loading of the module can cause a malfunction, failure or

 

drop.When using the PLC in the environment of much vibration, tighten

 

the module with a screw.

 

Tighten the screw in the specified torque range. Undertightening can

 

cause a drop, short circuit or malfunction. Overtightening can cause a

 

drop, short circuit or malfunction due to damage to the screw or

 

module.

 

When installing more cables, be sure that the base unit and the module

 

connectors are installed correctly. After installation, check them for

 

looseness. Poor connections could cause an input or output failure.

 

Securely load the memory card by pushing it into the memory card

 

loading slot. Check for insecure loading after loading the memory card.

 

Not doing so can cause a malfunction due to a contact fault.

 

Completely turn off the external power supply before loading or

 

unloading the module. Not doing so could result in electric shock or

 

damage to the product.

 

Do not directly touch the module's conductive parts or electronic

 

components. Touching the conductive parts could cause an operation

 

failure or give damage to the module.

This section gives instructions for handling the CPU, I/O, intelligent function and power supply modules, base units and so on.

(1)Module enclosure, terminal block connectors and pin connectors are made of resin; do not drop them or subject them to strong impact.

(2)Do not remove modules' printed circuit boards from the enclosure in order to avoid changes in operation.

(3)Tighten the module fixing screws and terminal block screws within the tightening torque range specified below.

Location of Screw

Tightening Torque Range

Module fixing screw (M3 12 screw)

36 to 48 N cm

I/O module terminal block screw (M3 screw)

42 to 58 N cm

I/O module terminal block fixing screw (M3.5 screw)

66 to 89 N cm

Power supply module terminal screw (M3.5 screw)

66 to 89 N cm

(4)Be sure to install the power supply module in the Q3B, Q6B and QA1S6B. Even if the power supply module is not installed, when the I/O modules and intelligent function module installed on the base units are of light load type, the modules may be operated. In this case, because a voltage becomes unstable, we cannot guarantee the operation.

(5)When an extension cable is used, do not bind the cable together with the main circuit (high voltage, heavy current) line or lay them close to each other.

9 - 9