5 POWER SUPPLY MODULE
No. |
| Name | Application | |
1) |
| POWER LED | 5VDC power indicator LED | |
|
|
|
| 1) Turned ON when the whole system operates normally. |
|
|
|
| 2) Turned OFF (opened) when a stop error occurs in the CPU module. |
2) |
|
| terminals | 3) In a multiple CPU system configuration, turned OFF when a stop error occurs in |
| ERR | |||
|
|
|
| any of the CPU modules. |
|
|
|
| Normally off when loaded in an extension base unit. |
3) |
| FG terminal | Ground terminal connected to the shield pattern of the printed circuit board. | |
4) |
| LG terminal | Grounding for the power supply filter. The potential of | |
| Q64P and Q61SP terminal is 1/2 of the input voltage | |||
|
|
|
| |
5) |
| +24V, 24G terminals | Used to supply 24VDC power to inside the output module (using external wiring). | |
6) |
| Terminal screw | M3.5 × 7 screw | |
7) |
| Terminal cover | Protective cover of the terminal block | |
8) |
| Module fixing screw hole | Used to fix the module to the base unit. M3 × 12 screw | |
| (Tightening torque : 36 to 48N•cm) | |||
|
|
|
| |
9) |
| Module loading lever | Used to load the module into the base unit. | |
10) |
| Power input terminals | Used to connect a 100VAC power supply. | |
11) |
| Power input terminals | Used to connect a 200VAC power supply. | |
12) |
| Power input terminals | Used to connect a 100VAC to 200VAC power supply. | |
13) |
| Power input terminals | Used to connect a 24VAC power supply. | |
14) |
| Power input terminals | Used to connect a 100VAC/200VAC power supply. |
POINTS
(1)The
Do not input a voltage of 200 VAC into it or trouble may occur on the
Power | Supply power voltage | ||
module type | 100VAC | 200VAC | |
Operates normally. | Power supply module | ||
causes trouble. | |||
|
| ||
| Power supply module does |
| |
not cause trouble. | Operates normally. | ||
CPU module cannot be | |||
|
| ||
| operated. |
|
(2)Q64P automatically switches the input range 100/200VAC.
Therefore, it is not compatible with the intermediate voltage (133 to 169VAC). The CPU module may not work normally if the above intermediate voltage is applied.
(3)Ensure that the earth terminals LG and FG are grounded.
5 - 10 | 5 - 10 |