9 LOADING AND INSTALLATION
! DANGER | When connecting a peripheral device to the CPU module or connecting |
|
| a personal computer or the like to the special function module to |
|
| exercise control (data change) on the running PLC, configure up an |
|
| interlock circuit in the sequence program to ensure that the whole |
|
| system will always operate safely. |
|
| Also before exercising other control (program change, operating status |
|
| change (status control)) on the running PLC, read the manual carefully |
|
| and fully confirm safety. |
|
| Especially for the above control on the remote PLC from an external |
|
| device, an immediate action may not be taken for PLC trouble due to a |
|
| data communication fault. |
|
| In addition to configuring up the interlock circuit in the sequence |
|
| program, corrective and other actions to be taken as a system for the |
|
| occurrence of a data communication fault should be predetermined |
|
| between the external device and PLC CPU. |
|
|
|
|
CAUTION | Do not bunch the control wires or communication cables with the main |
|
| circuit or power wires, or install them close to each other. They should |
|
| be installed 100 mm (3.94 inch) or more from each other. |
|
| Not doing so could result in noise that would cause erroneous |
|
| operation. |
|
| When controlling items like lamp load, heater or solenoid valve using an |
|
| output module, large current (approximately ten times greater than that |
|
| present in normal circumstances) may flow when the output is turned |
|
| OFF to ON. Take measures such as replacing the module with one |
|
| having sufficient rated current. |
|
When the PLC power supply is switched |
| |
performed temporarily due to differences in delay time and starting time between the |
| |
PLC power supply and the external power supply for the controlled object (especially |
| |
DC). |
|
|
For example, if the external power supply for the controlled object is switched on in a |
| |
DC output module and then the PLC power supply is switched on, the DC output |
| |
module may provide false output instantaneously at |
| |
is necessary to make up a circuit that can switch on the PLC power supply first. |
| |
Also, an abnormal operation may be performed if an external power supply fault or |
| |
PLC failure takes place. |
| |
To prevent any of these abnormal operations from leading to the abnormal operation of |
| |
the whole system and in a |
| |
breakdown and accidents due to abnormal operations (e.g. emergency stop, protective | 9 | |
and interlock circuits) should be constructed outside the PLC. |
The following page gives examples of system designing in the above viewpoint.
9 - 2 | 9 - 2 |