11 TROUBLESHOOTING

MELSEC-Q

 

Error Code

Error Contents and Cause

Corrective Action

Corres-

 

ponding

 

(SD0)

1

 

 

 

 

CPU

 

 

 

 

 

 

 

 

 

In a multiple CPU system, the MELSECNET/H under control of

(1) Delete the MELSECNET/H network parameter of the

 

 

 

 

MELSECNET/H under control of another station.

 

 

 

 

another station is specified as the first I/O number in the network

 

 

 

 

(2) Change the setting to the first I/O number of the MELSECNET/H

 

 

 

 

setting parameter of the MELSECNET/H.

QCPU

 

 

 

under control of the host station.

 

 

 

The network parameters of the MELSECNET/H operating in the

 

function

 

 

 

ordinary station were rewritten to the control station, or the network

 

Ver. B

 

 

 

parameters of the MELSECNET/H operating in the control station

Reset the CPU module.

or later

 

 

 

were rewritten to the ordinary station.

 

 

 

 

(The network parameters are reflected on the module side by

 

 

 

 

 

making a reset.)

 

 

 

 

 

 

(1) The number of actually installed modules is different from that

(1) Check the network parameters and the installation state. If

 

 

3100

 

designated in the number of modules setting parameter of

inconsistency is found, arrange consistency between network

 

 

 

parameters and the installation state.

 

 

 

 

MELSECNET/H.

 

If network parameters are changed, write the new network

 

 

 

 

(2) The head I/O number of actually installed modules is different

 

 

 

 

parameters to the CPU module.

 

 

 

 

from that designated in the network parameter of

(2) Check the number of extension stages of the extension base unit.

QCPU

 

 

 

MELSECNET/H.

 

(3) Check the state of connection of the extension base unit and

 

 

 

 

 

 

 

 

(3) Some data in the parameter cannot be handled.

connector. If the display unit is connected to the main base unit

 

 

 

 

(4) The station type of MELSECNET/H has been changed while the

or extension base unit, check the state of connection.

 

 

 

 

(4) If the error persists after the above items (1) through (3) are

 

 

 

 

power is on. (RESET

RUN is required to change the station

 

 

 

 

checked, the hardware is faulty. Contact your nearest Mitsubishi

 

 

 

 

type.)

 

 

 

 

 

 

representative and explain the symptom.

 

 

 

 

Network parameters have not been written although the QnACPU is

(1) Write after correcting network parameters.

QnA

 

 

 

the control station, or the master station.

(2) If the error persists after corrections have been made, contact

 

 

 

your nearest Mitsubishi representative.

 

 

 

 

 

 

 

 

 

 

The link refresh range exceeded the file register capacity.

Change the file register file for the one refresh-enabled in the whole

QCPU

 

 

 

range.

 

 

 

 

 

 

 

 

 

 

function

 

 

 

• When the station number of the MELSECNET/H module is 0, the

Correct the type or station number of the MELSECNET/H module in

 

 

 

inter-PLC network parameter setting has been made.

Ver. B

 

 

 

• When the station number of the MELSECNET/H module is other

the parameter to meet the used system.

or later

 

 

 

than 0, the remote master parameter setting has been made.

 

 

 

 

 

 

 

(1) Check the network parameters and the installation state. If

 

 

 

 

 

 

inconsistency is found, arrange consistency between network

 

 

3101

 

The network No. specified by a parameter is different from that of

parameters and the installation state.

 

 

 

 

the actually mounted network.

If network parameters are changed, write the new network

 

 

 

 

The head I/O No. specified by a parameter is different from that of

parameters to the CPU module.

 

 

 

 

the actually mounted I/O unit.

(2) Check the number of extension stages of the extension base unit.

 

 

 

 

The network class specified by a parameter is different from that of

(3) Check the state of connection of the extension base unit and

 

 

 

 

the actually mounted network.

connector. If the display unit is connected to the main base unit

 

 

 

 

The network refresh parameter of the MELSECNET/10(H) is out of

or extension base unit, check the state of connection.

 

 

 

 

the specified area.

 

(4) If the error persists after the above items (1) through (3) are

 

 

 

 

 

 

checked, the hardware is faulty. Contact your nearest Mitsubishi

 

 

 

 

 

 

representative and explain the symptom.

 

 

3102

 

An error was discovered when the network parameter check was

(1) Write after correcting network parameters.

 

 

 

(2) If the error persists after corrections have been made, contact

 

 

 

made at the network module.

 

 

 

 

your nearest Mitsubishi representative.

 

 

 

 

 

 

 

 

 

 

In a multiple CPU system, the Q series Ethernet interface module

(1) Delete the Ethernet setting parameter of the Q series Ethernet

QCPU

 

 

 

interface module under control of another station.

function

 

 

 

under control of another station is specified as the first I/O number

 

 

 

(2) Change the setting to the first I/O number of the Q series

Ver. B

 

 

 

of the Ethernet setting parameter.

 

 

 

Ethernet interface module under control of the host station.

or later

 

 

 

 

 

 

 

 

• Though the number of Ethernet module is set to one or more in

(1) Write after correcting network parameters.

 

 

 

 

the parameter, the actually mounted number of units is zero.

 

 

 

 

(2) If the error persists after corrections have been made, contact

Rem

 

 

 

• The head I/O number for the Ethernet module set parameter is

 

3103

 

your nearest Mitsubishi representative.

 

 

different from that of the actually mounted module.

 

 

 

 

AJ71QE71 does not exist in the position of I/O number set by the

(1) Write after correcting network parameters.

 

 

 

 

parameter.

 

QnA

 

 

 

I/O number designation is overlapping.

(2) If the error persists after corrections have been made, contact

 

 

 

Numbers of the parameter and loaded AJ71QE71 are different.

your nearest Mitsubishi representative.

 

 

 

 

Ethernet (parameter + dedicated instruction) is set to more than 5.

 

 

 

 

 

 

 

 

 

 

 

Ethernet and MELSECNET/10 use the same network number.

(1) Write after correcting network parameters.

 

 

3104

 

Network number, station number or group number set by the

 

 

 

(2) If the error persists after corrections have been made, contact

 

 

 

parameter is out of range.

 

Rem

 

 

 

 

your nearest Mitsubishi representative.

 

 

 

I/O number is out of range.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

In a multiple CPU system, the Q series CC-Link module under

(1) Delete the CC-Link setting parameter of the Q series CC-Link

QCPU

 

 

 

module under control of another station.

function

 

 

 

control of another station is specified as the first I/O number of the

 

 

 

(2) Change the setting to the first I/O number of the Q series CC-

Ver. B

 

 

 

CC-Link setting parameter.

 

 

 

 

 

Link module under control of the host station.

or later

 

 

 

 

 

 

 

 

(1) Though the number of CC-Link module set in the network

 

 

 

3105

 

parameters is one or more, the actually mounted number of

(1) Write after correcting network parameters.

 

 

 

units is zero.

 

 

 

 

 

(2) The head I/O number in the common parameters is different

(2) If the error persists after corrections have been made, contact

Rem

 

 

 

from that of the actually mounted module.

your nearest Mitsubishi representative.

 

 

 

(3) The station class for the CC-Link module quantity set

 

 

 

 

 

parameters is different from that of the actually mounted station.

 

 

 

 

 

The contents of the Ethernet parameter are incorrect.

Write after correcting parameters.

QnA

 

 

 

 

 

 

 

 

 

 

 

 

Change the file register file for the one refresh-enabled in the whole

QCPU

 

 

 

The CC-Link link refresh range exceeded the file register capacity.

function

 

3106

 

range.

Ver. B

 

 

 

 

 

or later

 

 

 

The network refresh parameter for CC-Link is out of range.

Check the parameter setting.

QCPU

 

 

 

Rem

 

 

 

 

 

 

 

3107

 

The contents of the CC-Link parameter are incorrect.

Check the parameter setting.

Rem

 

 

 

 

 

 

 

3200

 

The parameter contents are incorrect.

 

 

 

3201

 

The contents of the SFC block attribute information are incorrect.

Write after correcting parameters.

 

 

3202

 

The number of step relays designated in the parameters is less than

 

 

 

 

the number used by the program.

 

 

 

3203

 

The execution type set for an SFC program in the parameters is

 

 

 

 

other than the scan execution type.

 

 

 

 

 

 

 

 

3300

 

The first I/O number in the intelligent function module parameter set

Check the parameter setting.

QCPU

 

 

on GX Configurator differs from the actual I/O number.

Rem

 

 

 

 

1 Characters in parentheses ( ) indicate the special register numbers where individual information is being stored.

11 - 30