11 TROUBLESHOOTING
| Error Code | Error Contents and Cause | Corrective Action | Corres- | ||
| ponding | |||||
| (SD0) | 1 | ||||
|
|
|
| CPU | ||
|
|
|
|
|
| |
|
|
| In a multiple CPU system, the MELSECNET/H under control of | (1) Delete the MELSECNET/H network parameter of the |
| |
|
|
| MELSECNET/H under control of another station. |
| ||
|
|
| another station is specified as the first I/O number in the network |
| ||
|
|
| (2) Change the setting to the first I/O number of the MELSECNET/H |
| ||
|
|
| setting parameter of the MELSECNET/H. | QCPU | ||
|
|
| under control of the host station. | |||
|
|
| The network parameters of the MELSECNET/H operating in the |
| function | |
|
|
| ordinary station were rewritten to the control station, or the network |
| Ver. B | |
|
|
| parameters of the MELSECNET/H operating in the control station | Reset the CPU module. | or later | |
|
|
| were rewritten to the ordinary station. |
| ||
|
|
| (The network parameters are reflected on the module side by |
|
| |
|
|
| making a reset.) |
|
|
|
|
|
| (1) The number of actually installed modules is different from that | (1) Check the network parameters and the installation state. If |
| |
| 3100 |
| designated in the number of modules setting parameter of | inconsistency is found, arrange consistency between network |
| |
|
| parameters and the installation state. |
| |||
|
|
| MELSECNET/H. |
| If network parameters are changed, write the new network |
|
|
|
| (2) The head I/O number of actually installed modules is different |
| ||
|
|
| parameters to the CPU module. |
| ||
|
|
| from that designated in the network parameter of | (2) Check the number of extension stages of the extension base unit. | QCPU | |
|
|
| MELSECNET/H. |
| (3) Check the state of connection of the extension base unit and | |
|
|
|
|
| ||
|
|
| (3) Some data in the parameter cannot be handled. | connector. If the display unit is connected to the main base unit |
| |
|
|
| (4) The station type of MELSECNET/H has been changed while the | or extension base unit, check the state of connection. |
| |
|
|
| (4) If the error persists after the above items (1) through (3) are |
| ||
|
|
| power is on. (RESET | RUN is required to change the station |
| |
|
|
| checked, the hardware is faulty. Contact your nearest Mitsubishi |
| ||
|
|
| type.) |
|
| |
|
|
|
| representative and explain the symptom. |
| |
|
|
| Network parameters have not been written although the QnACPU is | (1) Write after correcting network parameters. | QnA | |
|
|
| the control station, or the master station. | (2) If the error persists after corrections have been made, contact | ||
|
|
| your nearest Mitsubishi representative. |
| ||
|
|
|
|
|
| |
|
|
| The link refresh range exceeded the file register capacity. | Change the file register file for the one | QCPU | |
|
|
| range. | |||
|
|
|
|
| ||
|
|
|
|
| function | |
|
|
| • When the station number of the MELSECNET/H module is 0, the | Correct the type or station number of the MELSECNET/H module in | ||
|
|
| Ver. B | |||
|
|
| • When the station number of the MELSECNET/H module is other | the parameter to meet the used system. | or later | |
|
|
| than 0, the remote master parameter setting has been made. |
|
| |
|
|
|
|
| (1) Check the network parameters and the installation state. If |
|
|
|
|
|
| inconsistency is found, arrange consistency between network |
|
| 3101 |
| The network No. specified by a parameter is different from that of | parameters and the installation state. |
| |
|
|
| the actually mounted network. | If network parameters are changed, write the new network |
| |
|
|
| The head I/O No. specified by a parameter is different from that of | parameters to the CPU module. |
| |
|
|
| the actually mounted I/O unit. | (2) Check the number of extension stages of the extension base unit. |
| |
|
|
| The network class specified by a parameter is different from that of | (3) Check the state of connection of the extension base unit and |
| |
|
|
| the actually mounted network. | connector. If the display unit is connected to the main base unit |
| |
|
|
| The network refresh parameter of the MELSECNET/10(H) is out of | or extension base unit, check the state of connection. |
| |
|
|
| the specified area. |
| (4) If the error persists after the above items (1) through (3) are |
|
|
|
|
|
| checked, the hardware is faulty. Contact your nearest Mitsubishi |
|
|
|
|
|
| representative and explain the symptom. |
|
| 3102 |
| An error was discovered when the network parameter check was | (1) Write after correcting network parameters. |
| |
|
| (2) If the error persists after corrections have been made, contact |
| |||
|
| made at the network module. |
| |||
|
|
| your nearest Mitsubishi representative. |
| ||
|
|
|
|
|
| |
|
|
| In a multiple CPU system, the Q series Ethernet interface module | (1) Delete the Ethernet setting parameter of the Q series Ethernet | QCPU | |
|
|
| interface module under control of another station. | function | ||
|
|
| under control of another station is specified as the first I/O number | |||
|
|
| (2) Change the setting to the first I/O number of the Q series | Ver. B | ||
|
|
| of the Ethernet setting parameter. | |||
|
|
| Ethernet interface module under control of the host station. | or later | ||
|
|
|
|
| ||
|
|
| • Though the number of Ethernet module is set to one or more in | (1) Write after correcting network parameters. |
| |
|
|
| the parameter, the actually mounted number of units is zero. |
| ||
|
|
| (2) If the error persists after corrections have been made, contact | Rem | ||
|
|
| • The head I/O number for the Ethernet module set parameter is | |||
| 3103 |
| your nearest Mitsubishi representative. | |||
|
| different from that of the actually mounted module. |
| |||
|
|
| AJ71QE71 does not exist in the position of I/O number set by the | (1) Write after correcting network parameters. |
| |
|
|
| parameter. |
| QnA | |
|
|
| I/O number designation is overlapping. | (2) If the error persists after corrections have been made, contact | ||
|
|
| Numbers of the parameter and loaded AJ71QE71 are different. | your nearest Mitsubishi representative. |
| |
|
|
| Ethernet (parameter + dedicated instruction) is set to more than 5. |
|
| |
|
|
|
|
|
| |
|
|
| Ethernet and MELSECNET/10 use the same network number. | (1) Write after correcting network parameters. |
| |
| 3104 |
| Network number, station number or group number set by the |
| ||
|
| (2) If the error persists after corrections have been made, contact |
| |||
|
| parameter is out of range. |
| Rem | ||
|
|
|
| your nearest Mitsubishi representative. | ||
|
|
| I/O number is out of range. |
|
| |
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
| In a multiple CPU system, the Q series | (1) Delete the | QCPU | |
|
|
| module under control of another station. | function | ||
|
|
| control of another station is specified as the first I/O number of the | |||
|
|
| (2) Change the setting to the first I/O number of the Q series CC- | Ver. B | ||
|
|
|
| |||
|
|
|
| Link module under control of the host station. | or later | |
|
|
|
|
| ||
|
|
| (1) Though the number of |
|
| |
| 3105 |
| parameters is one or more, the actually mounted number of | (1) Write after correcting network parameters. |
| |
|
| units is zero. |
|
| ||
|
|
| (2) The head I/O number in the common parameters is different | (2) If the error persists after corrections have been made, contact | Rem | |
|
|
| from that of the actually mounted module. | your nearest Mitsubishi representative. | ||
|
|
| (3) The station class for the |
|
| |
|
|
| parameters is different from that of the actually mounted station. |
|
| |
|
|
| The contents of the Ethernet parameter are incorrect. | Write after correcting parameters. | QnA | |
|
|
|
|
|
|
|
|
|
|
|
| Change the file register file for the one | QCPU |
|
|
| The | function | ||
| 3106 |
| range. | Ver. B | ||
|
|
|
|
| or later | |
|
|
| The network refresh parameter for | Check the parameter setting. | QCPU | |
|
|
| Rem | |||
|
|
|
|
|
| |
| 3107 |
| The contents of the | Check the parameter setting. | Rem | |
|
|
|
|
|
| |
| 3200 |
| The parameter contents are incorrect. |
|
| |
| 3201 |
| The contents of the SFC block attribute information are incorrect. | Write after correcting parameters. |
| |
| 3202 |
| The number of step relays designated in the parameters is less than |
| ||
|
|
| the number used by the program. |
|
| |
| 3203 |
| The execution type set for an SFC program in the parameters is |
|
| |
|
| other than the scan execution type. |
|
| ||
|
|
|
|
| ||
| 3300 |
| The first I/O number in the intelligent function module parameter set | Check the parameter setting. | QCPU | |
|
| on GX Configurator differs from the actual I/O number. | Rem | |||
|
|
|
|
1 Characters in parentheses ( ) indicate the special register numbers where individual information is being stored.
11 - 30 | 11 - 30 |