11 TROUBLESHOOTING
11.2.12 Flowchart for when output load of output module does not turn on
The following shows the flowchart to be followed when the output load of the output module does not turn on during PLC operation.
The output load does not turn on.
Is the operation
indicator of output module
turned on?
YES
Is voltage for the power supply load added?
YES
What is the voltage
among the various output
COM terminals of the
output module?
Is it reaching the supply voltage value?
Output module failure Replace the output module.
Confirm rush current when the load is at the maximum simultaneous on.
OK
NO Check output conditions with the monitor mode of the GX Developer.
NO | Is the operation | Off | |||||
indicator of input module | |||||||
|
|
|
|
| |||
|
|
| turned on? |
|
| ||
|
|
|
| On |
|
| |
|
|
|
|
|
| ||
|
|
|
|
|
|
| |
0V |
| Set the GX Developer in the monitor |
|
| |||
|
|
| |||||
| mode and check that the input signal |
|
| ||||
|
|
|
| (Monitor signal off) | |||
|
|
| is OFF. |
| |||
|
|
|
|
|
| ||
|
|
|
|
|
| ||
|
|
| Check the power supply load wire |
| |||
|
|
|
| ||||
|
|
|
|
| |||
|
|
| and recover the power supply. |
|
| ||
|
|
|
|
|
|
|
Check the load wire and load, and recover the power supply.
NG |
| Change the output relay number and |
|
| |||
|
| let the load maximum simultaneous |
|
|
|
| |
|
| on current to within the specification. |
|
Voltage measurement among the modules input and COM terminals.
0V
Supply voltage
Check the external wiring and external input devices.
Please consult your local Mitsubishi service center or representative, explaining a detailed description of the problem.
POINT
For the trouble that the input signal to the input module is not turned off, troubleshoot referring to Section 11.5 Examples of I/O Modules Troubleshooting.
11 - 11 | 11 - 11 |