5POWER SUPPLY MODULE
(3)When the base unit is of QA1S6B:
Power supply module |
|
| Base unit |
A1S61PN, A1S62PN, |
|
| |
|
| QA1S65B and QA1S68B | |
A1S63P |
|
| |
|
|
| |
|
|
| I/O module |
|
|
| A1SX10, A1SY10, etc. |
Special function module |
| peripheral devices | |
A1SD61, |
| AD75TU | 2 |
2: Select the power supply module also in consideration of the current consumption of the peripheral devices connected to the special function module.
For example, when the AD75TU is connected to the
5.1.3 Precaution when connecting the uninterruptive power supply
Be sure of the following terms when connecting the High Performance model QCPU system to the uninterruptive power supply (abbreviated as UPS hereafter):
Use a UPS which employs the constant inverter power supply method with 5 % or less voltage fluctuation.
Do not use a UPS with the constant commercial power supply method.
5 - 8 | 5 - 8 |