2 SYSTEM CONFIGURATION FOR SINGLE CPU SYSTEM
(d) The modules shown below cannot be used.
Module Name | Type | |
MELSECNET/10 network | A1SJ71LP21, A1SJ71BR11, A1SJ71QLP21, | |
module | A1SJ71QLP21S, A1SJ71QLP21GE, A1SJ71QBR11 | |
MELSECNET (II), /B data link | A1SJ71AP21, A1SJ71AR21, A1SJ71AT21B | |
module |
| |
Ethernet interface module | ||
| ||
Serial communication module, | A1SJ71QC24(N), | |
computer link module |
| |
A1SJ61QBT11, A1SJ61BT11 | ||
Modem interface module | ||
A1SJ71ME81 |
(e)A dedicated instruction for the next module which was present in the QnA/A series program instruction cannot be used for the High Performance model QCPU.
Module Name | Type |
High speed counter module | A1SD61, A1SD62, |
Positioning module | |
ID module |
(f)Some system configurations and functions are restricted when writing the parameter of the "High speed interrupt fixed scan interval" setting.
Refer to the following manual for the restrictions when the parameter of the
"High speed interrupt fixed scan interval" setting has been written.
• High Performance model QCPU (Q mode) User's Manual
(Function Explanation, Program Fundamentals) Note that the above restrictions do not apply to the High Performance model QCPU of serial number "04011" or earlier since it ignores the "High speed interrupt fixed scan interval" setting.
(2) Software package
GX Developer that can use the functions added to the High Performance model QCPU changes depending on the function version/serial number of the CPU module.
| Function Version | Serial Number | GX Developer |
| A | — | Version 4 |
| — | Functions added to "02092" | Version 6 |
| B | — | |
|
| ||
| — | Functions added to "03052" | Version 7 |
| — | Functions added to "04012" | Version 7.10L |
| or later | ||
|
|
| |
| Refer to Section 2.3 to confirm the function version and serial number of the High | ||
| Performance model QCPU. |
| |
2 - 7 |
|
| 2 - 7 |