6 BASE UNIT AND EXTENSION CABLE
R1
I2
List for Calculating Voltage Drops Occurring at Extension Cables when connecting Q6B between Q3B and Q5B
Position of extension base unit | Voltage drop caused by extension | ||
cable from the main base unit to the | |||
Q6B | Q5B | ||
Q5B IN connector (V) | |||
Extension stage 1 | Extension stage 2 | V=(R1+R2)I1 | |
Extension stage 1, | Extension stage 3 | V=(R1+R2+R3)I1 | |
Extension stage 2 | |||
|
| ||
Extension stage 1 to 3 | Extension stage 4 | V=(R1+R2+R3+R4)I1 | |
Extension stage 1 to 4 | Extension stage 5 | V=(R1+R2+R3+R4+R5)I1 | |
Extension stage 1 to 5 | Extension stage 6 | V=(R1+R2+R3+R4+R5+R6)I1 | |
Extension stage 1 to 6 | Extension stage 7 | V=(R1+R2+R3+R4+R5+R6+R7)I1 |
The voltage supplied to the "IN" connector of the Q5B reaches 4.75 VDC or higher on the condition that the voltage drop (V) at the extension cable between the main base unit and Q5B is 0.15 VDC or lower.
(3)When the GOT is
(a) Selection condition
4.75VDC or higher should be supplied to the "IN" connector of the Q5B.
(b) How to calculate voltage to "IN" connector
The 5VDC output voltage of the power supply module on the main base unit is set to at least 4.90VDC.
Therefore, the Q5B can be used if the voltage drop is 0.15VDC or lower (4.9VDC - 4.75VDC = 0.15VDC).
| Main base unit (Q3 B) | Extension Cable | Extension Cable | ||||
Power |
|
|
| ||||
|
|
| Conductor | ||||
supply |
|
|
| Type | |||
module |
|
|
| Resistance ( ) | |||
| Extension base unit (Q5 B) | QC05B | 0.044 | ||||
| I1 |
|
|
| QC06B | 0.051 | |
|
|
|
| QC12B | 0.082 | ||
|
|
|
|
|
| ||
GOT |
|
|
| QC30B | 0.172 | ||
|
|
| QC50B | 0.273 | |||
|
|
|
|
|
| ||
|
|
|
|
|
| ||
|
|
|
|
|
| QC100B | 0.530 |
|
|
|
|
| Number of GOTs connected : Max. 5 units |
|
|
GOT |
|
|
|
| |||
|
|
|
| ||||
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Symbol | Description |
VVoltage drop at the extension cable between the main base unit and extension base unit (Q5B)
5VDC current consumption when the Q5B is used as Extension n+1, n = 1 to 5, n: Extension No. of the
In
Q6B connected
(Sum total of current consumed by Q5B and currents consumed by I/O, intelligent function modules loaded on the Q5B)
5VDC current consumption of the GOT (current consumption per GOT is 254mA)
Im
• Im = 254 c (c: Number of GOTs connected (c: 1 to 5))
Rn
Extension cable resistance between the main base unit or the extension base unit (Q6B) and extension base unit (Q6B)
Rn+1 Extension cable resistance between the extension base unit (Q6B) and extension base unit (Q5B)
6 - 10 | 6 - 10 |