11 TROUBLESHOOTING

MELSEC-Q

Special Relay List (Continued)

Number

Name

Meaning

Explanation

Set by

Corresponding

Applicable

(When Set)

ACPU

CPU

 

 

 

 

M9

 

 

 

 

 

 

SM250

Max. loaded I/O

OFF: Ignored

• When this relay goes from OFF to ON, maximum loaded

U

New

+Rem

read

ON : Read

I/O number is read to SD250.

 

 

 

• After the head I/O number of the I/O module being

 

 

 

 

 

 

replaced is set in SD251 is set, on-line I/O module

 

 

 

 

 

 

replace ment is enabled when this relay is ON.

 

 

 

 

 

 

(Only one module can be replaced at each setting.)

 

 

Q2A (S1)

SM251

I/O change flag

OFF: No replacement

• To replace an I/O module in the RUN status, use the

U (END)

M9094

ON : Replacement

program or a peripheral device to turn this relay ON; to

Q3A

 

 

 

 

 

 

 

replace an I/O module in the STOP status, turn this relay

 

 

Q4A

 

 

 

ON in the test mode of a peripheral device.

 

 

Q4AR

 

 

 

• Do not switch between RUN and STOP status until I/O

 

 

 

 

 

 

module replacement is completed.

 

 

 

SM252

I/O change OK

OFF: Replacement prohibited

• Goes ON when I/O replacement is OK.

S (END)

New

 

 

 

ON : Replacement enabled

 

 

 

 

 

 

 

• Effective for the batch refresh

 

 

 

SM254

All stations

OFF: Refresh arrival station

(also effective for the low speed cyclic)

U (Every

New

QCPU

 

refresh command

ON : Refresh all stations

• Designate whether to receive arrival stations only or to

END)

 

 

 

 

 

receive all slave stations.

 

 

 

 

 

OFF: Operative network

• Goes ON for standby network

 

 

 

SM255

 

(If no designation has been made concerning active or

S (Initial)

New

 

 

ON : Standby network

 

 

MELSECNET/10

standby, active is assumed.)

 

 

 

SM256

module 1

OFF: Reads

• For refresh from link to CPU (B, W, etc.) indicate whether

U

New

 

information

ON : Does not read

to read from the link module.

 

SM257

 

OFF: Writes

• For refresh from CPU to link (B, W, etc.), designate

U

New

 

 

ON : Does not write

whether to write to the link module.

 

 

 

 

 

 

 

 

OFF: Operative network

• Goes ON for standby network

 

 

 

SM260

 

(If no designation has been made concerning active or

S (Initial)

New

 

 

ON : Standby network

 

 

MELSECNET/10

standby, active is assumed.)

 

 

 

SM261

module 2

OFF: Reads

• For refresh from link to CPU (B, W, etc.) indicate whether

U

New

 

information

ON : Does not read

to read from the link module.

 

SM262

 

OFF: Writes

• For refresh from CPU to link (B, W, etc.), designate

U

New

 

 

ON : Does not write

whether to write to the link module.

 

 

 

 

 

 

 

 

OFF: Operative network

• Goes ON for standby network

 

 

 

SM265

 

(If no designation has been made concerning active or

S (Initial)

New

 

 

ON : Standby network

 

 

MELSECNET/10

standby, active is assumed.)

 

 

 

SM266

module 3

OFF: Reads

• For refresh from link to CPU (B, W, etc.) indicate whether

U

New

 

information

ON : Does not read

to read from the link module.

 

SM267

 

OFF: Writes

• For refresh from CPU to link (B, W, etc.), designate

U

New

 

 

ON : Does not write

whether to write to the link module.

 

 

 

 

 

 

 

 

OFF: Operative network

• Goes ON for standby network

 

 

 

SM270

 

(If no designation has been made concerning active or

S (Initial)

New

 

 

ON : Standby network

 

 

MELSECNET/10

standby, active is assumed.)

 

 

 

SM271

module 4

OFF: Reads

• For refresh from link to CPU (B, W, etc.) indicate whether

U

New

 

information

ON : Does not read

to read from the link module.

 

SM272

 

OFF: Writes

• For refresh from CPU to link (B, W, etc.), designate

U

New

 

 

ON : Does not write

whether to write to the link module.

 

 

 

 

 

 

 

 

 

• Goes ON when a CC-Link error is detected in any of the

S (Status

 

QCPU

 

 

 

installed QJ61QBT11.

New

 

 

 

change)

Remote

SM280

CC-Link error

OFF: Normal

Goes OFF when normal operation is restored.

 

 

 

 

ON : Error

• Goes ON when a CC-Link error is detected in any of the

 

 

 

 

 

 

 

 

 

 

 

installed A(1S)J61QBT11.

S (Error)

New

QnA

 

 

 

Stays ON even after normal operation is restored.

 

 

 

SM320

Presence/absenc

OFF: SFC program absent

• ON if SFC program is correctly registered, and OFF if not

S (Initial)

M9100

 

e of SFC

ON : SFC program present

registered.

 

 

program

• Goes OFF if SFC dedicated instruction is not correct.

 

 

 

 

 

 

 

 

 

 

 

• Initial value is set at the same value as SM320.

 

 

 

 

 

 

(Goes ON automatically if SFC program is present.)

 

 

 

 

 

 

• SFC program will not execute if this goes OFF prior to

 

 

 

SM321

Start/stop SFC

OFF: SFC program stop

SFC program processing

S (Initial)

M9101

 

 

program

ON : SFC program start

• Starts SFC program when this relay goes from OFF to

U

format change

 

 

 

 

ON.

 

 

 

 

 

 

• Stops SFC program when this relay goes from ON to

 

 

 

 

 

 

OFF.

 

 

 

11 - 45