6 BASE UNIT AND EXTENSION CABLE

6.6 Guideline for Use of Extension Base Units (Q5†B)

MELSEC-Q

Since the Q5†B is supplied with 5VDC from the power supply module on the main base unit, a voltage drop occurs at extension cables.

Improper I/O may be provided if the specified voltage (4.75VDC or higher) is not supplied to the "IN" connector of the Q5†B.

When using the Q5†B, make sure that the "IN" connector of the Q5†B is supplied with 4.75VDC or higher.

And it is recommend to connect it with the shortest possible extension cable right after connecting the main base unit, so as to minimize the effects of voltage drop.

(1)When only the Q5†B is connected to the extension base unit

(a)Selection condition

4.75VDC or higher should be supplied to the "IN" connector of the Q5†B in the final extension stage.

(b) How to calculate voltage to "IN" connector

V1 R1

V2 R2

R7 R7

The 5VDC output voltage of the power supply module on the main base unit is set to at least 4.90VDC.

Therefore, the Q5†B can be used if the voltage drop is 0.15VDC or lower (4.9VDC - 4.75VDC = 0.15VDC).

 

Main base unit (Q3 B)

 

 

Extension Cable

Power

 

 

Extension Cable

 

 

Conductor

supply

 

 

Type

module

 

 

Resistance ( )

 

 

 

 

 

 

 

 

 

Extension base unit (Q5

B)

QC05B

0.044

 

 

 

Extension stage 1

QC06B

0.051

l1

 

 

QC12B

0.082

 

 

 

 

 

 

 

 

 

 

 

 

QC30B

0.172

Extension base unit (Q5

B)

QC50B

0.273

 

 

 

 

l2

 

Extension stage 2

QC100B

0.530

 

 

 

Extension base unit (Q5B)

Extension stage 7

l7

Symbol

Description

V1

Voltage drop at the extension cable between the main base unit and extension base unit

Vn

Voltage drop at the extension cable between the extension base unit (extension stage n-1) and extension base

unit (extension stage n)

 

R1

Cable resistance between the main base unit and extension base unit

Rn

Cable resistance between the extension base unit (extension stage n-1) and extension base unit (extension

stage n)

 

l1 to l7

5VDC current consumption among extension stage 1 to 7 1

1: Sum total of current consumed by Q5†B and currents consumed by the I/O, intelligent function modules loaded on the Q5†B.

The symbols including "I" (I1 to I7) vary with the modules loaded on the extension base unit. For details of the symbol, refer to the user's manuals of the module used.

6 - 8