8EMC AND LOW VOLTAGE DIRECTIVE
(b)Positioning modules
Precautions to be followed when the machinery conforming to the EMC Directive is configured using the
1)When wiring with a 2 m (6.56 ft.) or less cable
•Ground the shield section of the external wiring cable with the cable clamp. (Ground the shield at the closest location to the A1SD75 external wiring connector.)
•Wire the external wiring cable to the drive unit and external device with the shortest practicable length of cable.
•Install the drive unit in the same panel.
Power supply module
A1SD75 module
External wiring connector
Cable clamp
External wiring cable (within 2 m (6.56 ft.))
Drive unit
Power supply module
2)When wiring with cable that exceeds 2 m (6.56 ft.), but is 10 m (32.79 ft.) or less
•Ground the shield section of the external wiring cable with the cable clamp. (Ground the shield at the closest location to the A1SD75 external wiring connector.)
•Install a ferrite core.
•Wire the external wiring cable to the drive unit and external device with
the shortest practicable length of cable.
| A1SD75 module |
|
|
|
|
| External wiring connector |
|
|
|
| ||||
|
|
|
|
|
| Ferrite core | |
|
|
|
|
|
|
| |
|
|
|
|
|
|
| Cable clamp |
|
|
|
|
|
|
|
|
External wiring cable (2 m to 10 m (6.56 ft. to 32.79 ft.))
Drive unit
3)Ferrite core and cable clamp types and required quantities
•Cable clamp
Type : AD75CK (Mitsubishi Electric)
•Ferrite core
Type :
•Required quantity
Cable length | Prepared part |
| Required Qty |
| |
1 axis | 2 axes | 3 axes | |||
|
| ||||
Within 2 m (6.56 ft.) | AD75CK | 1 | 1 | 1 | |
2 m (6.56 ft.) to 10m | AD75CK | 1 | 1 | 1 | |
(32.79ft.) | 1 | 2 | 3 |
8 - 6 | 8 - 6 |