11 TROUBLESHOOTING

11.2.5 Flowchart for when the "RUN" LED is turned off

MELSEC-Q

The following shows the flowchart to be followed when the "RUN" LED of the CPU module turns off during PLC operation.

"RUN" LED is turned off.

Is the "POWER" LED of

the power supply module lit?

YES

Is "ERR." LED on/flickering?

NO

NO

 

Proceed to Section 11.2.4,

 

 

 

 

"Flowchart for when the "POWER"

 

 

 

 

 

 

LED is turned off."

 

 

 

 

 

 

 

 

 

YES

 

Proceed to Section 11.2.7,

 

 

 

 

"Flowchart for when the "ERR." LED

 

 

 

 

 

 

is on/flickering."

 

 

 

 

 

Reset the CPU module RESET/L. CLR switch.

"RUN" LED is off.

Set the CPU module's RUN/STOP switch to STOP and write END to address 0 with the GX Developer.

Set the RUN/STOP switch to RUN and enter to the monitor mode with the GX Developer to be operated.

"RUN" LED is on.

Considered to be a sequence program error.

Check the program and modify the program error location.

"RUN" LED

 

 

 

 

 

 

 

 

 

 

 

 

 

 

is on.

 

 

(1)

PLC part/connection fault

 

 

 

 

 

(2)

By excessive noise

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

For the case of (1)

For the

 

 

 

 

 

 

case of (2)

Please consult your local Mitsubishi service center or representative, explaining a detailed description of the problem.

"RUN" LED does not turn on.

Connect a surge protector circuit such as CR to the noise source.

NO

Can "RUN" LED

 

 

be turned on?

 

 

 

YES

 

 

 

 

 

 

 

 

 

Completion