4 AUXILIARY AND APPLIED FUNCTIONS
POINT
(1)After completion of SSCNET communication disconnect processing, be sure to check the LED display of the servo amplifier for "AA" before turning OFF its the power supply.
(2)When a "1 to 32 : Disconnect command" and/or
(3)When "1 to 32 : Disconnect command" is set to axis not disconnect, the connect/disconnect status device (SD508) returns "0" without entering the status of
(4)Operation failure may occur in some axes if the power supply of servo amplifiers connected after them on the SSCNET system is turned OFF. Be sure to use the disconnect function before turning OFF the power supply of any servo amplifiers connected after an amplifier whose power remains on.
(3)Procedure for connect/disconnect function to exchange the servo amplifier or SSCNET cable is shown below.
(a)Operation procedure to disconnect
1)Set the axis No. to disconnect in SD803. (Setting value: 1 to 32)
2)Check that
3)Set
4)Check that "0: Disconnect command accept waiting" is set in SD508. (Completion of disconnection)
5)Turn OFF the power supply of servo amplifier after checking its LED display for "AA" and then disconnect.