APPENDICES

 

Error code

Error contents and cause

Corrective action

 

(SD0)

 

 

 

 

1000

 

 

 

1001

 

 

 

1002

 

 

 

1003

Runaway or failure of CPU module.

 

 

1004

(1) Take noise reduction measures.

 

(1) Malfunctioning due to noise or other reason

 

1005

(2) Reset the CPU module and RUN it again. If the same error is

 

(2) Hardware fault

 

1006

displayed again, this suggests a CPU module hardware fault.

 

 

 

1007

 

Explain the error symptom and get advice from our sales

 

1008

 

representative.

 

 

 

 

1009

 

 

 

1105

The CPU shared memory in the CPU module is faulty.

 

 

1150

The memory of the CPU module in the Multiple CPU high speed

 

 

transmission area is faulty.

 

 

 

 

 

1300

There is an output module with a blown fuse.

Check FUSE. LED of the output modules and replace the module whose

 

LED is lit.

 

 

 

 

 

 

Set the Motion module/intelligent function module used in the Motion CPU

 

 

There was no response from the Motion module/intelligent function

in the system setting.

 

1401

This suggests a Motion module, intelligent function module, CPU module

 

module in the initial processing.

 

 

and/or base unit is expecting a hardware fault.

 

 

 

 

 

 

Explain the error symptom and get advice from our sales representative.

 

 

(1) An error is detected at the intelligent function module.

The CPU module, base unit and/or the intelligent function module that

 

1403

(2) The I/O module (including intelligent function module) is nearly

was accessed is experiencing a hardware fault.

 

 

removed or completely removed/mounted during running.

Explain the error symptom and get advice from our sales representative.

 

1413

An error is detected on the system bus.

 

 

1414

Reset the CPU module and RUN it again. If the same error is displayed

 

 

 

1415

Fault of the main or extension base unit was detected.

again, the intelligent function module, CPU module or base unit is faulty.

 

1416

System bus fault was detected at power-on or reset.

Explain the error symptom and get advice from our sales representative.

 

 

 

 

 

 

APP - 17