3 COMMON PARAMETERS
3.2.3 I/O number settingSet the modules installed in the each slot of the main base or extension base and assign the control CPU of applicable slot as the self CPU in the system setting for Motion CPU.
The following modules must be set the I/O No.. |
| |
• Input module | • Output module | • Input/Output composite module |
• Analogue input module | • Analogue output module |
Refer to the help of MT Developer for the detailed operating procedure on the system settings screen.
Set the I/O No. of modules controlled with the Motion CPU module set in the system structure screen of MT Developer. The setting procedure of I/O No. is shown below.
(Example) For set the output module
<System Structure>
1)
<Motion Slot Settings>
2) Select the I/O module.
3) Click [Detail Setting].
<I/O Module Settings>
4) Set the first I/O No. (PX No., PY No.).
5) Select applicable module type and number of points for
the I/O module to be used.
6) Click [OK].
(Note): Display of system setting and motion slot setting are different depending on the operating system software.
POINT
I/O No.s cannot be assigned automatically, unlike a PLC CPU for which I/O No. are assigned automatically if such setting is omitted in the Motion CPU. In the Motion CPU, be sure to set the first I/O No. in System Settings for each module used.
3 - 18