APPENDICES
| Error code | Error contents and cause | Corrective action |
| (SD0) | ||
|
|
| |
|
|
| Reset the CPU module and RUN it again. If the same error is displayed |
| 1430 | The error of self CPU is detected in the Multiple CPU high speed bus. | again, this suggests a CPU module hardware fault. |
|
|
| Explain the error symptom and get advice from our sales representative. |
|
|
| (1) Take noise reduction measures. |
|
|
| (2) Check the main base unit mounting status of the CPU module. |
|
| The communication error with other CPU is detected in the Multiple | (3) Reset the CPU module and RUN it again. If the same error is |
| 1431 | displayed again, this suggests a CPU module or base unit hardware | |
| CPU high speed bus. | ||
|
| fault. | |
|
|
| |
|
|
| Explain the error symptom and get advice from our sales |
|
|
| representative. |
|
| The communication time out with other CPU is detected in the | Reset the CPU module and RUN it again. If the same error is displayed |
| 1432 | again, this suggests a CPU module hardware fault. | |
| Multiple CPU high speed bus. | ||
|
| Explain the error symptom and get advice from our sales representative. | |
|
|
| |
| 1433 |
| (1) Take noise reduction measures. |
| 1434 |
| (2) Check the main base unit mounting status of the CPU module. |
| The communication error with other CPU is detected in the Multiple | (3) Reset the CPU module and RUN it again. If the same error is displayed | |
|
| ||
|
| CPU high speed bus. | again, this suggests a CPU module or base unit hardware fault. |
| 1435 |
| Explain the error symptom and get advice from our sales |
|
|
| representative. |
| 1500 | A momentary power supply interruption has occurred. | Check the power supply. |
| The power supply went off. | ||
|
|
| |
|
| (1) The battery voltage in the CPU module has dropped below |
|
| 1600 | stipulated level. | (1) Change the battery. |
| (2) The battery holder unit that install the battery is not mounted to the | (2) Mount the battery holder unit that installs the battery. | |
|
| ||
|
| CPU module. |
|
|
| In the I/O assignment setting of PLC CPU, the intelligent function | Make the PLC parameter's I/O assignment setting again so it is consistent |
| 2100 | with the actual status of the intelligent function module and the CPU | |
| module was allocated to an I/O module or vice versa. | ||
|
| module. | |
|
|
| |
| 2107 | The first I/O No. set in the system settings is overlapped with the one | Make the I/O No. setting again so it is consistent with the actual status of |
| for another module. | the modules. | |
|
| ||
| 2124 | (1) A module is mounted on the 65th or higher slot. | (1) Remove the module mounted on the 65th or later slot. |
| (2) The extension base unit set to "None" is mounted. | (2) Remove the extension base unit set to "None". | |
|
| ||
|
|
| (1) Install an usable module. |
| 2125 | (1) A module which the CPU cannot recognise has been mounted. | (2) The intelligent function module is experiencing a hardware fault. |
| (2) There was no response form the intelligent function module. | Explain the error symptom and get advice from our sales | |
|
| ||
|
|
| representative. |
|
| The motion modules (Q172DLX, Q172DEX, Q173DPX, Q172LX, |
|
| 2140 | Q172EX | Remove the Motion modules installed CPU slot or I/O 0 to 2 slot. |
|
| I/O 0 to 2 slot. |
|
|
| In a Multiple CPU system, the control CPU of intelligent function | (1) Change to the intelligent function module (function version B or later) |
|
| compatible with the Multiple CPU system. | |
| 2150 | module incompatible with the Multiple CPU system is set to other than | |
| (2) Change the control CPU of intelligent function module incompatible with | ||
|
| CPU No.1. | the Multiple CPU system to CPU No.1. |
|
|
|
APP - 19