2 MULTIPLE CPU SYSTEM

(b)When a stop error occurs in the CPU module for which " All station stop by stop error of CPU 'n' " has not been set, a "MULTI EXE. ERROR (error code: 7010)" error occurs in all other CPUs but operations will continue.

POINT

(Note-1) : When a stop error occurs, a "MULTI CPU DOWN (error code : 7000)" stop error will occur at the CPU on which the error was detected. Depending on the timing of error detection, a "MULTI CPU DOWN" error may be detected in a CPU of "MULTI CPU DOWN" status, not the first CPU on which a stop error occurs.

Because of this, CPU No. different from the one of initial error CPU may be stored in the error data's common information category.

To restore the system, remove the error cause on the CPU that is stopped by an error other than "MULTI CPU DOWN".

In the screen below, the cause of the CPU No.2 error that did not cause the "MULTI CPU DOWN" error is to be removed.

(c)Observe the following procedures to restore the system.

1)Confirm the error-detected CPU No. and error cause with the PLC diagnostics on GX Developer.

2)If the error code occurred in Motion CPU 10000 to 10999, confirm the error cause with Motion CPU error batch monitor of MT Developer.

3)Remove the error cause.

4)Either reset the PLC CPU No.1 or restart the power to the Multiple CPU system (power ON OFF ON).

All CPUs on the entire Multiple CPU system will be reset and the system will be restored when PLC CPU No.1 is reset or the power to the Multiple CPU system is reapplied.