2 MULTIPLE CPU SYSTEM

POINT

Selecting "Advanced setting" enables the ability to change the number of points from 1k to 2k in the system area used for Motion dedicated PLC instructions. Changing the number of points in the system area to 2k increases the number of Motion dedicated PLC instructions that can be executed concurrently in a scan. The screen where "Advanced setting" is selected is shown below.

Refer to the "Q173DCPU/Q172DCPU Motion controller (SV13/SV22) Programming Manual (Motion SFC) " for the Motion dedicated PLC instruction.

 

 

Setting/display value

 

Data size

Item

Setting description

Restriction

consistency

(Points: Word in units)

 

 

 

check

 

 

 

 

 

 

 

• Set the total of all CPUs to

 

 

 

 

be the following points or

 

 

 

 

lower.

 

CPU specific

Set the number of points of data

Range: 0 to 14k [points]

When constituted with two

 

CPUs: 14k [points]

Provided

send range

that each CPU module sends.

Unit: 1k [points]

When constituted with

 

 

 

 

 

 

 

 

three CPUs: 13k [points]

 

 

 

 

When constituted with four

 

 

 

 

CPUs: 12k [points]

 

 

Set the number of points for a

 

 

 

 

system area to be assigned for

 

 

 

System area

each CPU module.

Range: 1k/2k [points]

Provided

 

(Default value of system area

 

 

 

 

size is 1k [point].)

 

 

 

 

Display the total of number of

 

 

 

Total

points of the self CPU send area

Range: 1 to 16k [points]

Set the total of all CPUs to

and the system area that are

Unit: 1k [points]

16.0k points or lower.

 

assigned to the each CPU

 

 

 

 

 

 

module.

 

 

 

2 - 20