3COMMON PARAMETERS(2)Parameters common throughout the Multiple CPU system

In the Motion CPU, during initialization the parameters in the table below are verified against the parameters in the PLC CPU of CPU No. 1. Unmatched parameters generate a PARAMETER ERROR (error code: 3012, 3015), so the parameters show below must be set identically between Motion CPUs and the PLC CPU of CPU No.1. (If the system settings are changed in a Motion CPU, it is necessary to reset. Therefore, the parameters are checked only during initialization.)

The parameter No. of unmatched parameter is set in the error individual information (SD16) by this error occurrence.

PLC CPUs can use the parameters of the other CPUs via "Multiple CPU parameter utilization" of GX Developer. Since Motion CPUs don't have this function, however, the common parameters must be set for each Motion CPU.

Table of Parameters cross-Multiple CPU system

 

 

Type of parameter

 

 

Verification item

Parameter

Remark

 

Name in Motion CPU

 

Name in PLC CPU

number

 

 

 

 

 

 

No. of CPU

 

 

No. of PLC

 

Number of CPUs

0E00H

 

 

Operating mode

 

 

Operating mode

 

Operation mode for CPU

0E01H

 

 

 

 

 

stop error

 

 

 

 

 

 

 

 

 

 

 

CPU specific

 

 

CPU specific

Points of CPU specific

E008H

Refer to Section 2.3.2.

 

 

send range

 

 

send range

send range

 

 

 

 

 

 

 

 

 

Multiple

 

 

 

 

 

Refer to Section 2.3.2.

Multiple

Multiple CPU

System area

Multiple CPU

System area

System area size

E008H

This parameter can be

high speed

CPU

high speed

set when "Advanced

CPU setting

 

 

 

 

 

 

settings

 

 

 

 

 

transmission

 

transmission

 

 

 

 

setting" is selected.

 

area setting

 

 

area setting

 

 

 

 

Refer to Section 2.3.2.

 

 

Automatic

 

 

Automatic

Points of automatic

E009H

(Automatic refresh using

 

 

refresh setting

 

 

refresh setting

refresh

Multiple CPU high speed

 

 

 

 

 

 

 

 

 

 

 

 

 

 

transmission area)

 

Multiple CPU synchronous

 

Multiple CPU synchronous

Synchronize Multiple CPU

E00BH

Refer to Section 2.3.5.

 

startup setting

 

 

startup setting

 

startup or not

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Verify module only set in

Motion slot setting

 

 

Detailed settings

Control PLC

Control CPU No.

0406H

the system settings in the

 

 

 

I/O

 

 

 

 

 

Motion CPU side.

 

 

 

 

 

 

 

 

 

 

 

 

assignment

 

 

 

 

 

 

 

 

 

 

 

Total number of bases

 

Not verified if base

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Base No.

 

Base setting

 

 

 

Basic setting

Slots

 

0401H

settings are omitted in

 

 

 

Base

Number of base

 

 

 

 

 

 

 

the PLC CPU side.

 

 

 

 

 

 

 

slots

 

 

3 - 5