Product Specifications
The following sections detail the input, output and environmental specifications for the UPS system.
SystemModelsNotes
Powerware BPIII HE 50 | 50 kVA, 40kW | 50 | Hz/60 Hz models |
Powerware BPIII HE 62.5 | 62.5 kVA, 50kW | 50 | Hz/60 Hz models |
Powerware BPIII HE 75 | 75 kVA, 60kW | 60 | Hz models |
System Input
Operating Input | 208 VAC for operation from 177 VAC to 229 VAC (60 Hz only) |
Voltage | 400 VAC for operation from 340 VAC to 440 VAC (50 Hz only) |
| 480 VAC for operation from 408 VAC to 528 VAC (60 Hz only) |
| 600 VAC for operation from 510 VAC to 660 VAC (60 Hz only) |
|
|
Operating Input | 3 Hz of nominal (60 Hz) |
Frequency Range |
|
|
|
Operating Input | Battery Charge: |
Current | 125% of full load for overload + battery charge |
| Actual load + 25% of full load for battery charge |
| Reduced for Generator: |
| Adjustable, set to 102% |
|
|
Input Current | 10% maximum over zero to full load based on 10% THD at full |
Harmonic Content | load (with input filter option installed) |
|
|
Power | Typically |
|
|
Power Factor | Minimum 0.9 |
|
|
Line Surges | 6 kV OC, 3 kA SC per ANSI 62.41 and IEC |
|
|