Product Specifications

The following sections detail the input, output and environmental specifications for the UPS system.

SystemModelsNotes

Powerware BPIII HE 50

50 kVA, 40kW

50

Hz/60 Hz models

Powerware BPIII HE 62.5

62.5 kVA, 50kW

50

Hz/60 Hz models

Powerware BPIII HE 75

75 kVA, 60kW

60

Hz models

System Input

Operating Input

208 VAC for operation from 177 VAC to 229 VAC (60 Hz only)

Voltage

400 VAC for operation from 340 VAC to 440 VAC (50 Hz only)

 

480 VAC for operation from 408 VAC to 528 VAC (60 Hz only)

 

600 VAC for operation from 510 VAC to 660 VAC (60 Hz only)

 

 

Operating Input

3 Hz of nominal (60 Hz)

Frequency Range

 

 

 

Operating Input

Battery Charge:

Current

125% of full load for overload + battery charge

 

Actual load + 25% of full load for battery charge

 

Reduced for Generator:

 

Adjustable, set to 102%

 

 

Input Current

10% maximum over zero to full load based on 10% THD at full

Harmonic Content

load (with input filter option installed)

 

 

Power Walk-In

Typically 15---20 second rectifier ramp-up to full utility load

 

 

Power Factor

Minimum 0.9

 

 

Line Surges

6 kV OC, 3 kA SC per ANSI 62.41 and IEC 801---4

 

 

Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operation

121

164201261 Rev. F 111503

Page 129
Image 129
Powerware 5075 kVA operation manual Product Specifications, System Input