Powerware 5075 kVA operation manual Using the Menu Options, Setup

Models: 5075 kVA

1 162
Download 162 pages 48.55 Kb
Page 63
Image 63

Using the Menu Options

The UPS menus allow you to display data in the information area to help you monitor and control UPS operation. The following menus and options are available:

Meters Displays UPS performance meters for the system or critical load.

Events Displays the list of Active System Events and a historical log of system events.

Statistics Displays statistical information about UPS operations for the battery, load, or line.

Graphics Displays a real-time graphic representation of the flow of current through the internal UPS components.

Setup

Allows you to configure the UPS communications port and set

the date and time for the timestamp.

Figure 25 shows the LCD screen as it appears when you first start the UPS. The Meters menu is displayed in the menu box, with the System option highlighted. In the information area, the system meters show their current readings.

 

 

Uninterruptible Power System

 

 

 

 

System Normal

 

 

 

 

 

 

04 MAY 1998

14:25:45

Alarm:

None

 

 

 

 

 

 

 

 

 

 

Notice: None

 

 

 

 

 

 

 

 

 

 

Battery

 

Input

 

 

 

Output

 

Percent

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

100%

VAB

VBC

VCA

FREQ

VAB

VBC

VCA

FREQ

 

 

 

 

480

480

480

60.0

480

480

480

60.0

 

 

IA

IB

 

 

IC

IA

IB

 

IC

IN

 

 

88

88

 

 

88

90

90

 

90

000

 

 

KVA

KW

 

 

PF

 

KVA

KW

PF

 

 

 

73

69

 

0.95

 

75

60

0.80

Meters

 

 

 

 

 

 

 

 

 

 

System

 

Bypass

 

 

 

Battery

 

Load Amps

 

 

 

 

 

 

 

 

 

 

 

 

VAB

VBC

 

VCA

 

V

 

I

 

 

 

480

480

 

480

 

540

 

000

 

Meters

Events

Statistics Graphics

Setup

 

 

 

 

 

Figure 25. System Meters Screen (Typical for Powerware BPIII HE 75 480/480V Unit)

The Input area shows the phase-to-phase voltage, frequency, and phase current of the incoming utility, followed by the KVA, KW, and power factor measurements. The output area shows the same information for the power being output by the UPS.

The Bypass area shows the phase-to-phase voltage of the bypass source. The Battery area displays the DC voltage (V) and the DC current (I) at the inverter side of the DC to DC voltage converter.

Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operation

55

164201261 Rev. F 111503

Page 63