Table K. Communications Panel Inputs and Outputs
TB2 Pin # | Name | Description | |
1 | REMOTE EPO | Contacts used to activate remote EPO of UPS. | |
|
| ||
2 | REMOTE EPO RTN | ||
| |||
|
|
| |
3 |
|
| |
4 | ON INV | Contacts used to indicate On Inverter status of UPS. | |
|
| ||
5 | ON INV RTN | ||
| |||
|
|
| |
6 | ON BYPASS | Contacts used to indicate On Bypass status of UPS. | |
|
| ||
7 | ON BYPASS RTN | ||
| |||
|
|
| |
8 | BATTERY CONTACTOR | Contacts used to indicate UPS Battery Contactor is | |
CLOSED | |||
| |||
|
| closed. | |
9 | BATTERY CONT RTN | ||
| |||
|
|
| |
10 | RELAY 1 NO |
| |
|
|
| |
11 | RELAY 1 NC | General purpose NO and NC relay contacts. | |
|
|
| |
12 | ALARM RTN |
| |
|
|
| |
13 | RELAY 2 NO |
| |
|
|
| |
14 | RELAY 2 NC | General purpose NO and NC relay contacts. | |
|
|
| |
15 | NOTICE RTN |
|
DESCRIPTION: INSTALLATION NOTES
DRAWING NO: |
SHEET: 9 of 11
|
|
|
| REVISION: A | DATE: 053099 |
| |
|
|
|
|
| |||
|
| ||||||
Powerware BPIII Harsh Environment UPS |