Meters Printout (Ctrl + M)

This key sequence prints the current readings of the UPS system meters. The Input area shows the phase-to-phase voltage, frequency, and phase current of the incoming utility, followed by the kVA, kW, and power factor measurements. The output area shows the same information for the power being output by the UPS. The Bypass area shows the phase-to-phase voltage of the bypass source. The Battery area displays the DC voltage (V) and the DC current (I). Figure 45 shows a sample Meters printout.

 

 

Uninterruptible Power System

 

UPS System Normal

 

03 JAN 1994 14:22:49

Alarm:

None

 

 

 

 

 

 

Notice:

None

 

 

 

 

 

 

 

 

Input

 

Output

 

VAB

VBC

VCA FREQ

VAB

VBC

VCA

FREQ

480

480

480 60.0

208

208

208

60.0

 

IA

IB

IC

IA

IB

IC

IN

 

88

88

88

222

222

222

0

 

KVA

KW

PF

 

KVA

KW PF

 

73

69

0.95

 

80

64 0.80

 

 

Bypass

 

Battery

 

VAB

VBC

VCA

 

V

+

I

 

480

480

480

 

540

 

0

Figure 45. System Meters

System Information Printout (Ctrl + A)

This key sequence prints a listing of all available serial data. This printout contains the information shown on the Event History Log and Meters screens of the UPS (both Figures 44 and 45).

94

Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation

164291261 Rev. F 111503

Page 102
Image 102