94 Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation
164291261Rev. F 111503
Meters Printout (Ctrl + M)

This key sequence prints the current readings of the UPS system meters. The

Input area shows the phase-to-phase voltage, frequency, and phase current of the

incoming utility,fo llowedby the kVA, kW, and power factor measurements. The

output area showsthe same information for the power being output by the UPS.

TheBypassareashowsthephase-to-phasevoltageofthebypasssource.The

Battery area displaysthe DC voltage (V) and the DC current (I). Figure 45 shows

a sample Meters printout.

Input Output
Bypass Battery
VAB
480
VBC VCA
KW
69
KVA
73
IA IB IC
FREQ
60.0
PF
0.95
V
540
I
0
88
480 480
8888
VAB
480
VBC VCA
480 480
IA IB IC
222 222222
IN
0
VAB
208
VBC VCA
208 208
FREQ
60.0
KVA
80
KW
64
PF
0.80
Uninterruptible Power System
UPS System Normal
Alarm: None
Notice: None
03 JAN 1994 14:22:49

+

Figure45. System Meters
System Information Printout (Ctrl + A)

This key sequence prints a listing of all available serial data. This printout contains

the informationshown on the Event History Log and Meters screens of the UPS

(both Figures 44 and 45).