Table C. INPUT/OUTPUT Ratings & External Wiring Requirements for
Powerware BPIII HE 50 and 62.5 kVA (400 Volt)
|
| Ratings | Units |
| Rating | |
|
|
| 50 Hz | |||
|
|
|
|
| ||
Basic unit rating at |
| KVA | 50 | 62.5 | ||
0.8 lagging PF load |
| KW | 40 | 50 | ||
|
|
| INPUT/OUTPUT | 400 | 400 | |
|
|
| VOLTAGE | |||
|
|
|
|
| ||
| AC Input to UPS Rectifier | Amps (max) | 120 | 140 | ||
| Full Load + Batt. Chg. | |||||
A | (.95min.PF) | 3 , (1) gnd |
|
|
| |
|
|
|
|
| ||
C |
|
| AWG or | 2/0 | 3/0 | |
| Minimum conductor size | |||||
I |
| (number per ) | kcmil(ea) | (1) | (1) | |
N | AC Input to Bypass |
|
|
| ||
P |
|
|
| |||
Full Load Current | Amps (Nom) | 72 | 90 | |||
U | ||||||
| 3 , (1) gnd |
|
|
| ||
T |
|
|
|
| ||
|
|
|
|
| ||
| Minimum conductor size | AWG or | 3 | 1 | ||
|
| (number per ) | kcmil(ea) | (1) | (1) | |
D | DC Input from Battery to UPS |
|
|
| ||
C | (1) positive, (1) negative | VDC | 120 | 120 | ||
|
|
| Float VDC | 135 | 135 | |
I |
|
| Amps | 360 | 455 | |
N |
|
| (2.0V/cell) |
|
| |
P | Minimum conductor size | AWG or | 3/0 | 250 | ||
U | ||||||
T | (number per pole) | kcmil(ea) | (3) | (3) | ||
A | AC Output to Critical Load | Amps (Nom) | 72 | 90 | ||
C | Full Load Current3 | |||||
O | 3 , (1) Neutral, (1) gnd |
|
|
| ||
|
|
|
|
| ||
U | Minimum conductor size |
|
|
| ||
T | AWG or | 3 | 1 | |||
P |
| (number per ) | kcmil(ea) | (1) | (1) | |
U |
|
|
|
|
| |
T |
|
|
|
|
|
NOTE: Callout letter , , , and map to drawing
DESCRIPTION: | INSTALLATION NOTES | |||
DRAWING NO: |
| SHEET: 3 of 11 | ||
REVISION: F |
| DATE: | 115103 |
Powerware BPIII Harsh Environment UPS |