Table C. INPUT/OUTPUT Ratings & External Wiring Requirements for

Powerware BPIII HE 50 and 62.5 kVA (400 Volt)

 

 

Ratings

Units

 

Rating

 

 

 

50 Hz

 

 

 

 

 

Basic unit rating at

 

KVA

50

62.5

0.8 lagging PF load

 

KW

40

50

 

 

 

INPUT/OUTPUT

400

400

 

 

 

VOLTAGE

 

 

 

 

 

 

AC Input to UPS Rectifier

Amps (max)

120

140

 

Full Load + Batt. Chg.

A

(.95min.PF)

3 , (1) gnd

 

 

 

 

 

 

 

 

C

 

 

AWG or

2/0

3/0

 

Minimum conductor size

I

 

(number per )

kcmil(ea)

(1)

(1)

N

AC Input to Bypass

 

 

 

P

 

 

 

Full Load Current

Amps (Nom)

72

90

U

 

3 , (1) gnd

 

 

 

T

 

 

 

 

 

 

 

 

 

 

Minimum conductor size

AWG or

3

1

 

 

(number per )

kcmil(ea)

(1)

(1)

D

DC Input from Battery to UPS

 

 

 

C

(1) positive, (1) negative

VDC

120

120

 

 

 

Float VDC

135

135

I

 

 

Amps

360

455

N

 

 

(2.0V/cell)

 

 

P

Minimum conductor size

AWG or

3/0

250

U

T

(number per pole)

kcmil(ea)

(3)

(3)

A

AC Output to Critical Load

Amps (Nom)

72

90

C

Full Load Current3

O

3 , (1) Neutral, (1) gnd

 

 

 

 

 

 

 

 

U

Minimum conductor size

 

 

 

T

AWG or

3

1

P

 

(number per )

kcmil(ea)

(1)

(1)

U

 

 

 

 

 

T

 

 

 

 

 

NOTE: Callout letter , , , and map to drawing #164201261---3

DESCRIPTION:

INSTALLATION NOTES

DRAWING NO:

164201261---1

 

SHEET: 3 of 11

REVISION: F

 

DATE:

115103

A---4

Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation

164291261 Rev. F 111503

Page 136
Image 136
Powerware 5075 kVA operation manual Powerware Bpiii HE 50 and 62.5 kVA 400 Volt