Environmental Specifications

Operating Temperature

0 to 50˚C without derating. However, operating

 

at or near 50˚C will adversely affect battery life

 

(refer to your battery specifications for more

 

information). The recommended operating

 

temperature is 25˚C.

 

 

Operating Altitude

Maximum 1500m (5000 ft) at 50_C without

 

derating

 

 

Storage Temperature

---20 to +70˚C (prolonged storage above 40˚C

 

will cause rapid battery self-discharge)

 

 

Relative Humidity (operating and

95% maximum noncondensing

storage)

 

 

 

Acoustical Noise

75 dBA at a 1m distance

 

 

EMI Supression

Meets FCC Part 15 for class A devices

 

 

Electrostatic Discharge (ESD)

Meets IEC 801---2 specifications. Withstands up

Immunity

to 25 kV without damage and with no

 

disturbance or adverse effect to the critical load.

 

 

Battery Specifications

These specifications are for batteries supplied by the customer. Refer to Battery Data section for more information.

Nominal Battery String

120 VDC (60 cells)

Voltage

 

 

 

Float Charging

2.25 VDC per cell

 

(135 VDC based on 60 cells)

 

 

Initialize Charge

150 VDC, when inverter DC link set to 572 VAC

 

 

Battery Charge Current

Limited to 35% of full plus 6 Kw, regardless of actual load

Limit

on inverter

 

 