The Monitor Panel contains:

1.A flat liquid crystal display (LCD) screen.

2.A horizontal row of pushbuttons.

3.A vertical column of backlit status indicators.

4.A red EMERGENCY POWER OFF pushbutton.

A quick reference label describing how to use the Monitor Panel is located below the Monitor Panel. The following sections describe the Monitor Panel in detail.

Using the LCD Screen

The LCD screen at the top of the Monitor Panel provides an operator interface with the UPS. Figure 24 identifies the display fields discussed in the following sections.

A

B

C D

E

 

 

Uninterruptible Power System

 

 

 

 

F

System Normal

 

 

 

 

 

 

04 MAY 1998

14:23:45

Alarm:

None

 

 

 

 

 

 

 

 

 

 

Notice: None

 

 

 

 

 

 

 

 

 

 

 

Battery

 

Input

 

 

 

Output

 

G

Percent

 

 

 

 

 

 

 

 

 

 

 

100%

VAB

VBC

VCA

FREQ

VAB

VBC

VCA

FREQ

 

 

 

 

 

 

480

480

480

60.0

480

480

480

60.0

 

 

 

IA

IB

 

 

IC

IA

IB

 

IC

IN

 

 

 

88

88

 

 

88

90

90

 

90

000

 

 

 

KVA

KW

 

 

PF

 

KVA

KW

PF

 

 

 

 

73

69

 

0.95

 

75

60

0.80

 

Meters

 

 

 

 

 

 

 

 

 

 

 

System

 

Bypass

 

 

 

Battery

 

 

Load Amps

 

 

 

 

 

 

 

 

 

 

 

 

 

VAB

VBC

 

VCA

 

V

 

I

 

 

 

 

480

480

 

480

 

540

 

000

 

 

Meters

Events

Statistics Graphics

Setup

 

 

 

 

 

 

Figure 24. Parts of the LCD Screen (Typical for Powerware BPIII HE 75 480/480V Unit)

A The UPS status area contains three lines that display the current state of the UPS. The first line shows the present operational mode of the UPS. The second line shows the highest level of the current active alarms, and the third line shows any notices the UPS has posted. (For more information about alarms and notices, refer to Chapter 12 --- Responding to System Events.)

B The battery charge box shows the percentage of battery capacity available.

C The menu box shows the currently selected menu and lists the options available on that menu. The title at the top of the menu box is also shown below on the menu bar (E). Press the and pushbuttons to scroll up and down through the options in the menu box.

 

 

 

52

Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation

164291261 Rev. F 111503

Page 60
Image 60
Powerware 5075 kVA operation manual Using the LCD Screen, Red Emergency Power OFF pushbutton